INFINITY CONTROLLED LOW AMBIENT COOLING
NOTE: When this unit is operating below 55°F (13°C) outdoor
temperature, provisions must be made for low ambient operation.
This unit is capable of low ambient cooling down to 0°F
is not required, and the outdoor fan motor does not need to be
replaced for Infinity controlled low ambient operation. Low
ambient cooling must be enabled in the UI
begin to cycle until about 40°F (4°C).OAT. Fan will cycle based
on coil and outdoor air temperature. Infinity controlled low ambient mode operates as follows:
•In high stage, fan is off when outdoor coil temp is <outdoor air
temperature plus 3 ° F (1.7 ° C) or outdoor fan has been ON for 30
minutes. (Fan is turned off to allow refrigerant system to stabilize.)
•In low stage, fan is off when outdoor coil temp is <outdoor air
temperature plus 1 °F (.6°C) or outdoor fan has been ON for 30
minutes. (Fan is turned off to allow refrigerant system to stabilize.)
•In high stage and low stage, fan is on when outdoor coil temp >
outdoor air temperature plus 25 °F (13.8 ° C) or outdoor coil temp > 80°F (27°C) or if outdoor fan has been OFF for 30 minutes.
(Fan is turned on to allow refrigerant system to stabilize.)
•
motor is turned off for 10 minutes with the compressor running. If
LPS closes within 10 minutes then cooling continues with the
outdoor fan cycling per the coil temperature routine listed above for the remainder of the cooling cycle. If the LPS does not close within 10 minutes, then the normal LPS trip response (shut down
cooling operation and generate LPS trip error) will occur.
DEHUMIDIFICATION MODE
This Infinity system can be used to dehumidify the living space.
See UI Installation Instructions for more details.
SEQUENCE OF OPERATION-GAS HEAT
NOTE: Infinity control must be grounded for proper operation or control will lock out.
NOTE: If a power interruption occurs during a call for heat, the
control will start a
amber LED light will flash code 12 during the
after which the LED will be ON continuously, as long as no faults
are detected. After the
GAS HEAT MODE AND ADJUSTMENTS
When the UI calls for gas heat, the Infinity furnace board performs
a
1. Inducer
up on high speed, the pressure switch closes, and the
Infinity ignition control on the furnace board begins a 15
second
remain closed, the inducer will remain running. After the
pressure switch
begin a 15 second
2.
for 3 seconds. The main gas valve relay contact closes to energize the gas valve on low stage. After 5 seconds, the
igniter is
period begins. | NOTE: | The unit | always | lights on | high |
speed inducer and low stage gas valve operation. |
| ||||
3. | When | the burner | flame | is proved | at the |
sensor, | the furnace | control | determines | what |
heating stage to run based on feedback from the UI. If the UI is asking for low stage gas heat, the ignition control will
change the inducer speed to low speed and keep the gas valve energized on low stage. If the UI is asking for high stage gas heat, the ignition control will maintain running the
inducer on high speed and energize the gas valve's high stage relay to increase gas flow.
If the burner flame is not proved within 2 seconds, the control will
close the | gas valve | and | repeat | the | ignition sequence up to 3 more | ||||
before | going | to | Lockout | ||||||
will reset | automatically | after | 3 | hours, | by | momentarily | interrupting | ||
230 VAC | power, | or by | interrupting |
| 24 | VAC power | at SEC1 or | ||
SEC2 to the furnace board. |
|
|
|
|
|
|
If flame is proved when there should be no flame present, control
will lock out of | mode and operate the inducer motor | ||||||||||
until flame is no longer proved. |
|
|
|
|
|
| |||||
4. |
| Delay: |
| If the | burner | flame | is | proven, | |||
| approximately | 37 | seconds after | the gas | valve is opened | the | |||||
| Indoor Blower | is | turned on to the appropriate | speed | for | the | |||||
| gas heating | stage. |
|
|
|
|
|
|
|
| |
Simultaneously, | the | humidifier | terminal | HUM | and | electronic | air | ||||
cleaner | terminal |
|
| are | energized | throughout | the | heating | |||
cycle. |
|
|
|
|
|
|
|
|
|
|
|
NOTE: |
| terminal | is | common | with L2 and will have | ||||||
| when | unit | is powered. |
|
|
|
|
5.
the gas valve is
the burners, and
inducer motor will remain on for a
period. The indoor blower and air cleaner terminal
will remain energized for 90, 120, 150, or 180 seconds
(depending on selection of
UI). The
CHECK GAS INPUT (NATURAL GAS)
[]NIT DAMAGE HAZARD
Failure to follow this caution may result in component
damage.
Do not redrill an orifice. Improper drilling (burrs,
and misdirection of burner flame. If orifice hole appears
damaged or it is suspected to have been redrilled, check
orifice hole with a numbered drill bit of correct size.
FIRE HAZARD
Failure to follow this warning could result in personal iniury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screws.
This can result in unregulated manifold pressure and result
in excess overfire and heat exchanger failures.