![Economizer Hood and Two-Position Hood —](/images/new-backgrounds/33923/3392319x1.webp)
Economizer Hood and Two-Position Hood —
NOTE: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1.The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bot- tom of the indoor coil access panel. See Fig. 10.
filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 12.
DIVIDER
OUTSIDE
50HCQA
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
SIDE
PANEL
TOP
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
C06025
AIR
HOOD
CLEANABLE
ALUMINUM FILTER FILTER
BAROMETRIC RELIEF
FILTER CLIP
C08634
Fig. 12 - Economizer Filter Installation
6.Caulk the ends of the joint between the unit top panel and the hood top.
7.Replace the filter access panel.
Fig. 10 - Indoor Coil Access Panel Relocation
2.Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 11.
Step 9 — Install External Condensate Trap and Line
The unit has one
LEFT |
|
HOOD |
|
SIDE | 19 1/16”B |
| (483mm) |
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
33 3/8”
(848mm)
HOOD DIVIDER
C06026
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a
Fig. 11 - Economizer Hood Construction
3.Remove the shipping tape holding the economizer ba- rometric relief damper in place.
4.Insert the hood divider between the hood sides. See Fig. 11 and 12. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
5.Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom
CONDENSATE PAN (SIDE VIEW) |
| ALTERNATE | ||
STANDARD | DRAIN PLUG | |||
BOTTOM DRAIN | ||||
SIDE DRAIN | ||||
|
|
C08021
Fig. 13 - Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 14.
10