Table 8 – RTU-MP Controller Inputs and Outputs
|
| POINT NAME | BACnet OBJECT |
| TYPE OF I/O | CONNECTION PIN |
|
| NAME |
| NUMBERS | ||
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| INPUTS |
|
| |
Space Temperature Sensor | sptsens |
| AI (10K Thermistor) | |||
|
|
|
|
| ||
Supply Air Temperature | sat |
| AI (10K Thermistor) | |||
|
|
|
|
| ||
Local Outside Air Temperature Sensor | oatsens |
| AI (10K Thermistor) | |||
Space Temperature Offset Pot | sptopot |
| AI (100K Potentiometer) | |||
|
|
|
|
| ||
Indoor Air Quality | iaq |
| AI | |||
|
|
|
|
| ||
Outdoor Air Quality | oaq |
| AI | |||
Safety Chain Feedback | safety |
| DI (24 VAC) | |||
Compressor Safety | compstat |
| DI (24 VAC) | |||
|
|
|
|
| ||
Fire Shutdown | firedown |
| DI (24 VAC) | |||
|
|
|
|
| ||
Enthalpy Switch | enthalpy |
| DI (24 VAC) | |||
Humidistat Input Status | humstat |
| DI (24 VAC) | |||
|
|
| CONFIGURABLE | INPUTS* |
| |
Space Relative Humidity | sprh |
| AI | |||
|
|
|
|
|
| |
Outside Air Relative Humidity | oarh |
| AI | |||
|
| |||||
|
|
|
|
| ||
Supply Fan Status | fanstat |
| DI (24 VAC) | |||
|
|
|
|
|
| |
Filter Status | filtstat |
| DI (24 VAC) | |||
| J5 5,6 or | |||||
|
|
|
|
|
| |
Remote Occupancy Input | remocc |
| DI (24 VAC) | |||
|
| |||||
|
|
|
|
|
|
|
|
|
| OUTPUTS |
|
|
|
Economizer Commanded Position | econocmd |
| ||||
|
|
|
|
| ||
Supply Fan Relay State | sf |
| DO Relay (24VAC , 1A) | |||
Compressor 1 Relay State | comp_1 |
| DO Relay (24VAC , 1A) | |||
Compressor 2 Relay State | comp_2 |
| DO Relay (24VAC , 1A) | |||
|
|
|
|
| ||
Heat Stage 1 Relay State | heat_1 |
| DO Relay (24VAC , 1A) | |||
|
|
|
|
| ||
Heat Stage 2 Relay State | heat_2 |
| DO Relay (24VAC , 1A) | |||
Power Exhaust Relay State | aux_2 |
| DO Relay (24VAC , 1A) | |||
|
|
|
|
| ||
Dehumidification Relay State | humizer |
| DO Relay (24VAC, 1A) | |||
LEGEND |
|
|
|
| ||
AI | Analog Input |
|
|
|
| |
AO | Analog Output |
|
|
|
| |
DI | Discrete Input |
|
|
|
| |
DO | Discrete Output |
|
|
|
|
*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins
The
Supply Air Temperature (SAT) Sensor —
On
The SAT is
Outdoor Air Temperature (OAT) Sensor —
The OAT is
EconoMi$ert2 —
The
Outdoor air management functions can be enhanced with
Enthalpy control (outdoor air or differential sensors) Space CO2 sensor
Outdoor air CO2 sensor