Outdoor Air Temperature (OAT) Sensor —
The OAT is
EconoMi$ert2 —
The PremierLink control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the PremierLink control; EconoMi$er2 has no internal logic device.
Outdoor air management functions can be enhanced with
Enthalpy control (outdoor air or differential sensors) Space CO2 sensor
Outdoor air CO2 sensor
Refer to Table 3 for accessory part numbers.
Field Connections
Field connections for accessory sensor and input devices are made at the
Connect
TB1PL
SEN 1
SEN 3
C08212
Fig. 32 - PremierLink T-55 Sensor
Connect
50HCQA
1 | 2 | 3 | 4 | 5 | 6 | RED(+) |
|
|
|
|
|
| WHT(GND) | CCN COM | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| SEN |
| SET |
|
|
| SW1 |
|
|
|
| BLK |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| (T56) |
|
|
|
|
|
| BRN (GND) | SENSOR WIRING | |
|
|
|
|
| BLU (SPT) |
| |
|
|
|
|
|
|
| JUMPER |
|
|
|
|
|
|
| TERMINALS |
|
|
|
|
|
|
| AS SHOWN |
Table 4 provides a summary of field connections for units equipped with Space Sensor. Table 5 provides a summary of field connections for units equipped with Space Thermostat.
Space Temperature (SPT) Sensors —
Cool Warm
Fig. 33 - T-56 Internal Connections
C08202
The PremierLink controller is
1 | 2 | 3 | 4 | 5 | 6 | RED(+) |
|
|
|
|
|
| WHT(GND) | CCN COM | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| SEN |
|
|
|
|
| SW1 |
|
|
|
|
|
|
|
|
|
|
| BRN (GND) | SENSOR WIRING | |
|
|
|
|
| BLU (SPT) |
|
C08201
Fig. 31 - T-55 Space Temperature Sensor Wiring
| TB1 | PL |
SEN | 1 | |
| TB1 | PL |
SEN | 3 |
Jumper
SET
SET 5
C08213
Fig. 34 - PremierLink T-56 Sensor
Connect Thermostat —
A
If the 50HCQ unit is equipped with
19