If the 50HCQ unit has an economizer system and
Configure the Unit for Thermostat Mode —
Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode.
Differential Enthalpy Control —
Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.
Return Air Enthalpy Sensor —
Mount the
50HCQA
When the PremierLink is configured for Thermostat Mode, these functions are not available: Fire Shutdown (FSD), Remote Occupied (RMTOCC), Compressor Safety (CMPSAFE), Supply Fan Status (SFS), and Filter Pressure Switch (FILTER).
Economizer Controls
Outdoor Air Enthalpy Control (PNO 33CSENTHSW) —
The enthalpy control (33CSENTHSW) is available as a
– | 24V |
|
| RED |
| ||||
|
|
|
| |
Main | GND |
|
| BLK |
+ VDC |
|
| ||
|
|
|
| |
Out | LOW |
|
| GRA |
|
|
+
–
ECONO
MOTOR
ESL
damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate
Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled “ESL” to the terminal labeled “LOW”. See Fig. 36. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND).
C09027
Fig. 37 - Outside and Return Air Enthalpy Sensor
Wiring
To wire the return air enthalpy sensor, perform the following:
1. | Use a |
| to connect the return air enthalpy sensor to the enthal- |
| py controller. |
2. | Connect the |
| connector on the return air enthalpy sensor and the |
| (+) terminal on the enthalpy controller. Connect the |
Enthalpy |
|
|
Switch |
|
|
24V | RED |
|
GND | BLK |
|
LOW | GRA | ESL |
|
|
7
ECONO MOTOR
CTB
ECON
BLK wire to |
thalpy sensor and the |
controller. |
Indoor Air Quality (CO2 sensor) —
The indoor air quality sensor accessory monitors space carbon dioxide (CO2) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to
Factory Wiring Harness
C09026
Fig. 36 - Enthalpy Switch (33CSENTHSW) Connections
The outdoor enthalpy changeover setpoint is set at the enthalpy controller.
measure the levels of CO2 present in the space air.
The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 38 for typical CO2 sensor wiring schematic.
22