Carrier 50HCQA Rigging Details Positioning on Curb, Horizontal Conversion Panels

Models: 50HCQA

1 44
Download 44 pages 5.18 Kb
Page 8
Image 8
Fig. 5 - Rigging Details

50HCQA

C06005

 

MAX WEIGHT

 

 

DIMENSIONS

 

 

 

 

 

 

 

 

 

UNIT

 

A

 

B

 

C

 

 

 

 

 

 

LB

KG

IN

MM

IN

MM

IN

MM

 

 

 

 

 

 

 

 

 

50HCQA04

725

330

74.5

1890

38.5

980

33.5

850

 

 

 

 

 

 

 

 

 

50HCQA05

845

384

74.5

1890

37.5

955

41.5

1055

 

 

 

 

 

 

 

 

 

50HCQA06

900

409

74.5

1890

37.5

955

41.5

1055

 

 

 

 

 

 

 

 

 

NOTES:

1.Dimensions in ( ) are in millimeters.

2.Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.

Fig. 5 - Rigging Details

Positioning on Curb —

Position unit on roof curb so that the following clearances are maintained: 1/4 in. (6.4 mm) clearance between the roof curb and the base rail inside the front and rear, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately equal to Fig. 3, section C-C.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

After unit is in position, remove the compressor access panel. Holding the blocking between compressors with one hand, cut the strapping. Carefully remove the blocking without damaging tubing, wiring, or controls. Remove the strapping and replace the access panel.

Remove all shipping materials and top skid. Recycle or dispose of all shipping materials.

Step 7 — Convert to Horizontal and Connect Ductwork (when required)

Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return air smoke detector option may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 6.

C06108

Fig. 6 - Horizontal Conversion Panels

Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.

Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.

8

Page 8
Image 8
Carrier 50HCQA installation instructions Rigging Details Positioning on Curb, Horizontal Conversion Panels