Carrier 50HCQA Recommended Cables, Connecting CCN bus, Color Code Recommendations

Models: 50HCQA

1 44
Download 44 pages 5.18 Kb
Page 25
Image 25
Table 6 – Recommended Cables

signal pins must be wired to the signal ground pins. Wiring connections for CCN must be made at the 3-pin plug.

At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devices on any 1000-ft section. Optically isolated RS-485 repeaters are required every 1000 ft.

NOTE: Carrier device default is 9600 band.

Communications Bus Wire Specifications: The CCN Communication Bus wiring is field-supplied and field-installed. It consists of shielded 3-conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network.

See Table 6 for recommended cable.

Table 6 – Recommended Cables

MANUFACTURER

CABLE PART NO.

 

 

Alpha

2413 or 5463

 

 

American

A22503

 

 

Belden

8772

 

 

Columbia

02525

 

 

NOTE: Conductors and drain wire must be at least 20 AWG, stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of -20_C to 60_C is required. Do not run communication wire in the same conduit as or next to any AC voltage wiring.

The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communication bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only).

Connecting CCN bus:

NOTE: When connecting the communication bus cable, a color code system for the entire network is recommended to simplify installation and checkout. See Table 7 for the recommended color code.

Table 7 – Color Code Recommendations

SIGNAL TYPE

CCN BUS WIRE

CCN PLUG PIN

COLOR

NUMBER

 

 

 

 

+

Red

1

 

 

 

Ground

White

2

 

 

 

---

Black

3

 

 

 

Connect the CCN (+) lead (typically RED) to the unit’s TB1-12 terminal. Connect the CCN (ground) lead (typically WHT) to the unit’s TB1-14 terminal. Connect the CCN (-) lead (typically BLK) to the unit’s TB1-16 terminal. See Fig. 46.

CCN Bus

 

 

 

 

TB1

PL

+ (RED)

12

 

J2-1

 

TB1

GND (WHT) Connecting CCN bus:14 Table 7 – Color Code RecommendationsFig. 46 - PremierLink CCN Bus Connections J2-2

TB1

– (BLK) Manual background16 Manual backgroundManual background J2-3

C08276

Fig. 46 - PremierLink CCN Bus Connections

50HCQA

25

Page 25
Image 25
Carrier 50HCQA Recommended Cables, Connecting CCN bus, Color Code Recommendations, PremierLink CCN Bus Connections