Options and accessories
Factory-installed options
Cupronickel heat exchangers are available for higher corrosion protection for applications such as open tower, geothermal, etc. Consult the water quality guidelines for proper application and selection of this option.
Thermostat options include a unit mounted Manual Changeover (MCO) or Auto Changeover (ACO) thermo- stat. The temperature set point knob and push button switches for fan speed and cool/heat mode (MCO) selec- tion are conveniently located on the top. The thermostat senses the
Options R and S allow connection to a remote wall- mounted thermostat. The Complete C controller requires a heat pump thermostat. The Deluxe D controller can be configured for heat pump or heat/cool thermostat.
Extended range is provided to insulate the coaxial coil to prevent condensation, and therefore potential dripping problems, in applications where the entering water temperature is below the normal operating range (less than 60 F).
Cabinet options include a locking control panel for added security. Bottom or front return with left or right hand configurations are available for ease of installation. Available with 3 or 5 in. subbase, with or without motor- ized damper.
Motorized fresh air damper with the
Piping connections can be provided on either the right or left hand side of the unit, for easy installation. Orienta- tion is determined by facing the unit from the front side.
Automatic flow regulators include internally mounted
2.25or 3.0 gpm/ton automatic flow regulating valves for easier installation.
2.9and maximum operating pressure differential (MOPD) of 125 psi.
Mute package includes high density noise suppression material on front, right, and left sides of compressor compartment and
Deluxe D control system provides the same functions as the Complete C while incorporating additional flexibility and functions to include:
Thermostat input capabilities — Accommodate emergency shutdown mode and night setback with override (NSB) potential. Night setback from low temperature thermostat
with
Compressor relay staging — Used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in master/slave applications.
Boilerless electric heat control system — Allows automatic changeover to electric heat at low loop water temperature.
Intelligent reversing valve operation — Minimizes reversing valve operation for extended life and quiet operation.
Thermostat type select (Y, O or Y, W) — Provides ability to work and select heat pump or heat/cool thermostats (Y, W).
Reversing valve signal select (O or B) — Provides selection for heat pump O/B thermostats.
Dehumidistat input — Provides operation of fan control for dehumidification operation.
Multiple units on one thermostat/wall sensor — Provides for communication for up to three heat pumps on one thermostat.
Boilerless changeover temperature — Provides selection of boilerless changeover temperature set point.
Accessory relays — Allow configuration for multiple appli- cations including fan and compressor cycling, digital night setback (NSB), mechanical night setback, water valve oper- ation, and outside air damper operation.
Night low limit — If the unit operation is turned OFF from either the push button switches, remote thermostat or the energy management system, it is possible that the space temperature could drop uncontrollably. The Night Low Limit feature, with Deluxe D controller, helps maintain the space temperature at a level that is the best compromise between energy consumption and a safe space tempera- ture. A thermostat located near the return air filter activates the blower and compressor operation when the space temperature falls below 50 F. When return air tem- perature is raised above 55 F the compressor and blower stop.
Override function — An Override function is available for units operating in occupied/unoccupied mode under the control of an external timeclock or an energy management system. A contact closure from the timeclock or energy management system shorts the NSB and C terminal on the Deluxe D controller signaling an unoccupied mode.
For units with the
The units with the remote
PremierLink™ controller is compatible with the Carrier Comfort Network (CCN) and other building automation systems (BAS). This control is designed to allow users the access and ability to change