CORRECTION FACTORS — ENTERING AIR

 

HEATING

 

 

 

 

 

 

COOLING

 

 

 

 

 

EAT

 

Input

 

EAT

 

 

Sensible Capacity Entering Dry Bulb (F)

 

Power

 

DB

TC

THA

WB

TC

 

 

 

 

 

 

 

 

THR

Power

70

75

80

80.6

 

85

90

95

Input

(F)

 

 

(F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

1.011

0.989

1.007

60

0.893

0.889

1.087

*

*

 

*

*

*

0.964

0.902

65

1.004

0.994

1.004

65

0.964

0.692

0.884

1.085

1.108

 

*

*

*

0.988

0.967

68

1.002

0.997

1.002

66.2

0.983

0.645

0.838

1.036

1.059

 

1.231

*

*

0.995

0.985

70

1.000

1.000

1.000

67

1.000

0.613

0.806

1.000

1.027

 

1.199

*

*

1.000

1.000

75

0.996

1.007

0.995

70

1.049

0.683

0.879

0.902

 

1.077

1.274

1.415

1.016

1.046

80

0.991

1.018

0.990

75

1.118

0.676

0.698

 

0.866

1.068

1.266

1.037

1.106

*Sensible Capacity equals total capacity.

CORRECTION FACTORS — AIRFLOW

 

% OF

 

COOLING CORRECTIONS

 

HEATING CORRECTIONS

NOMINAL

TC

 

SC

Input

 

THR

TC

Input

THA

AIRFLOW

 

Power

 

Power

 

 

 

 

 

 

 

 

75%

0.951

 

0.860

0.963

 

0.952

0.990

1.054

0.966

 

81%

0.964

 

0.894

0.973

 

0.965

0.993

1.035

0.977

 

88%

0.979

 

0.936

0.984

 

0.979

0.996

1.019

0.987

 

94%

0.990

 

0.969

0.992

 

0.990

0.998

1.008

0.994

 

100%

1.000

 

1.000

1.000

 

1.000

1.000

1.000

1.000

 

106%

1.010

 

1.033

1.008

 

1.010

1.002

0.994

1.005

 

113%

1.019

 

1.069

1.016

 

1.019

1.003

0.988

1.011

 

 

LEGEND

 

 

 

 

 

 

DB

Dry Bulb

 

 

 

 

 

 

 

 

EAT — Entering Air Temperature (F)

 

 

 

 

 

 

SC

Sensible Capacity

 

 

 

 

 

 

TC

Total Capacity

 

 

 

 

 

 

 

 

THA — Total Heat of Absorption

THR — Total Heat of Rejection

50KQL CONSOLE BLOWER PERFORMANCE 60 Hz

 

RATED

AIRFLOW (cfm)

50KQL

AIRFLOW

Low Speed

High Speed

 

(cfm)

 

 

 

07

240

190

240

09

300

240

300

12

350

300

350

15

400

340

400

19

460

400

460

NOTES:

1.Fan speed is field adjustable.

2.All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 208 v for 208-230 v units.

3.All units are ARI/ISO 13256-1 rated on high fan speed.

4.All units are designed and rated for zero external static pressure (non-ducted) application.