Fig. 14 — 50RHE Blower Speed Selection

PSC (PERMANENT SPLIT CAPACITOR) BLOWER SPEED SELECTION — All Water Source Heat Pumps are factory set to deliver rated airflow at nominal static (37 Pa) on medium speed. Where higher static is needed, high speed can be utilized (100 to 125 Pa). Low speed will deliver approximately 85% of rated airflow (25 Pa). The PSC blower fan speed can be changed on all units by swapping wires connected to the relay contacts that control the fan. See Table 4 and Fig. 14.

NOTE: Available airflow for all units is shown in Table 4.

CONNECT THE BLUE WIRE TO:

H FOR HIGH SPEED FAN

M FOR MEDIUM SPEED FAN L FOR LOW SPEED FAN

BLU

MEDIUM FACTORY SETTING

H M L

FAN MOTOR

 

 

 

 

Fig. 14 — 50RHE Blower Speed Selection

 

 

Table 4 — 50RHE Blower Performance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50RHE

NOMINAL

MINIMUM

FAN

 

 

 

AIRFLOW (L/s)

 

 

AIRFLOW

AIRFLOW

 

 

External Static Pressure (Pa)

 

UNIT

SPEED

 

 

 

 

(L/s)

(L/s)

 

 

0

25

50

75

100

125

 

 

 

 

 

006

81

61

HI

 

133

123

112

89

78

MED

 

110

99

87

68

 

 

 

LO

 

98

90

75

 

 

 

 

60

009

113

85

HI

 

165

151

142

118

99

MED

 

160

146

127

113

94

 

 

 

LO

 

151

137

123

109

90

012

140

104

HI

 

170

165

151

137

123

109

MED

 

165

151

142

127

118

 

 

 

LO

 

146

137

127

118

104

015

212

160

HI

 

345

316

288

250

198

MED

 

321

302

274

241

189

 

 

 

LO

 

293

278

255

222

179

019

264

198

HI

 

326

311

283

250

203

MED

 

302

288

260

227

 

189

 

 

 

LO

 

293

269

245

217

179

024

307

231

HI

 

396

368

335

302

260

MED

 

387

359

326

297

255

 

 

 

LO

 

368

340

311

278

231

030

349

264

HI

 

529

496

463

425

378

330

MED

 

510

477

448

415

368

326

 

 

 

LO

 

458

439

406

378

340

297

036

437

326

HI

 

614

576

519

463

415

373

MED

 

580

543

488

434

392

349

 

 

 

LO

 

505

472

429

387

349

042

530

396

HI

 

743

691

629

566

501

435

MED

 

637

593

539

485

429

 

 

 

LO

 

498

463

421

048

630

472

HI

 

793

738

672

604

535

464

MED

 

777

723

658

592

524

455

 

 

 

LO

 

762

709

645

580

514

446

High Static

 

 

HI

 

757

668

552

630

472

MED

 

787

710

623

529

048

 

 

 

LO

 

797

748

690

612

516

 

 

 

 

060

790

595

HI

 

896

866

833

796

755

710

MED

 

818

803

779

747

707

658

 

 

 

LO

 

748

731

709

683

653

618

LEGEND

Shaded areas are below minimum CFM. This data is provided for troubleshooting information only.

NOTES:

1.Units factory shipped on medium speed. Other speeds require field selection.

2.For dual voltage units, airflow is rated at lowest voltage.

3.Performance data shown is based n wet coil and clean air filter.