Retry Mode — In Retry mode, the status LED will start to flash slowly to signal that the control is trying to recover from an input fault. The control will stage off the outputs and try to again satisfy the thermostat used to terminal Y. Once the ther- mostat input calls are satisfied, the control will continue normal operation.
NOTE: If 3 consecutive faults occur without satisfying the thermostat input call to terminal Y, the control will go into lockout mode. The last fault causing the lockout is stored in memory and can be viewed by entering Test mode.
Aquazone™ Deluxe D Control LED Indica- tors — There are 3 LED indicators on the D Control:
STATUS LED — Status LED indicates the current status or mode of the D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the D control is in test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will always flash a code representing the last fault in memory. If there is no fault in memory, the fault LED will flash code 1 on the and appear as 1 fast flash alternating with a
SERVICE
Perform the procedures outlined below periodically, as indicated.
IMPORTANT: When a compressor is removed from this unit, system refrigerant circuit oil will remain in the com- pressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.
IMPORTANT: All refrigerant discharged from this unit must be recovered without exception. Technicians must fol- low industry accepted guidelines and all local, state and fed- eral statutes for the recovery and disposal of refrigerants.
IMPORTANT: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians which meet local, state and federal proficiency requirements.
IMPORTANT: To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect switch before servicing unit.
Filters — Filters must be clean for maximum performance. Inspect filters every month under normal operating conditions. replace when necessary.
IMPORTANT: Units should never be operated with- out a filter.
Water Coil — Keep all air out of the water coil. Check open loop systems to be sure the well head is not allowing air to infiltrate the water line. Always keep lines airtight.
Inspect heat exchangers regularly, and clean more frequent- ly if the unit is located in a “dirty” environment. Keep the heat exchanger full of water at all times. Open loop systems should have an inverted P trap placed in the discharge line to keep water in the heat exchanger during off cycles. Closed loop systems must have a minimum of 105 kPa during the summer and 275 kPa during the winter.
Check P trap frequently for proper operation.
Table 15 — Aquazone™ D Control Current LED Status and Alarm Relay Operations
DESCRIPTION | STATUS LED | TEST LED | FAULT LED (Red) | ALARM RELAY | |
(Green) | (Yellow) | ||||
|
|
| |||
Normal Mode | On | Off | Flash Last Fault Code in Memory | Open | |
Normal Mode with PM | On | Off | Flashing Code 8 | Cycle (closed 5 sec, | |
open 25 sec, …) | |||||
|
|
|
| ||
D Control is | Off | Off | Off | Open | |
Test Mode | — | On | Flash Last Fault Code in Memory | Cycling Appropriate Code | |
Night Setback | Flashing Code 2 | — | Flash Last Fault Code in Memory | — | |
ESD | Flashing Code 3 | — | Flash Last Fault Code in Memory | — | |
Invalid | Flashing Code 4 | — | Flash Last Fault Code in Memory | — | |
No Fault in Memory | On | Off | Flashing Code 1 | Open | |
HP Fault | Slow Flash | Off | Flashing Code 2 | Open | |
LP Fault | Slow Flash | Off | Flashing Code 3 | Open | |
FP1 Fault | Slow Flash | Off | Flashing Code 4 | Open | |
FP2 Fault | Slow Flash | Off | Flashing Code 5 | Open | |
CO Fault | Slow Flash | Off | Flashing Code 6 | Open | |
Over/Under Voltage | Slow Flash | Off | Flashing Code 7 | Open (closed after 15 minutes) | |
HP Lockout | Fast Flash | Off | Flashing Code 2 | Closed | |
LP Lockout | Fast Flash | Off | Flashing Code 3 | Closed | |
FP1 Lockout | Fast Flash | Off | Flashing Code 4 | Closed | |
FP2 Lockout | Fast Flash | Off | Flashing Code 5 | Closed | |
CO Lockout | Fast Flash | Off | Flashing Code 6 | Closed |
LEGEND
CO — Condensate Overflow
ESD — Emergency Shutdown
FP — Freeze Protection
HP — High Pressure
LP — Low Pressure
PM — Performance Monitor
NOTES:
1.If there is no fault in memory, the Fault LED will flash code 1.
2.Codes will be displayed with a
3.Slow flash is 1 flash every 2 seconds.
4.Fast flash is 2 flashes every 1 second.
5.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a
23