Carrier 50RHE006-060 specifications Service

Models: 50RHE006-060

1 32
Download 32 pages 52.62 Kb
Page 23
Image 23
SERVICE

Retry Mode — In Retry mode, the status LED will start to flash slowly to signal that the control is trying to recover from an input fault. The control will stage off the outputs and try to again satisfy the thermostat used to terminal Y. Once the ther- mostat input calls are satisfied, the control will continue normal operation.

NOTE: If 3 consecutive faults occur without satisfying the thermostat input call to terminal Y, the control will go into lockout mode. The last fault causing the lockout is stored in memory and can be viewed by entering Test mode.

Aquazone™ Deluxe D Control LED Indica- tors — There are 3 LED indicators on the D Control:

STATUS LED — Status LED indicates the current status or mode of the D control. The Status LED light is green.

TEST LED — Test LED will be activated any time the D control is in test mode. The Test LED light is yellow.

FAULT LED — Fault LED light is red. The fault LED will always flash a code representing the last fault in memory. If there is no fault in memory, the fault LED will flash code 1 on the and appear as 1 fast flash alternating with a 10-second pause. See Table 15.

SERVICE

Perform the procedures outlined below periodically, as indicated.

IMPORTANT: When a compressor is removed from this unit, system refrigerant circuit oil will remain in the com- pressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.

IMPORTANT: All refrigerant discharged from this unit must be recovered without exception. Technicians must fol- low industry accepted guidelines and all local, state and fed- eral statutes for the recovery and disposal of refrigerants.

IMPORTANT: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians which meet local, state and federal proficiency requirements.

IMPORTANT: To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect switch before servicing unit.

Filters — Filters must be clean for maximum performance. Inspect filters every month under normal operating conditions. replace when necessary.

IMPORTANT: Units should never be operated with- out a filter.

Water Coil — Keep all air out of the water coil. Check open loop systems to be sure the well head is not allowing air to infiltrate the water line. Always keep lines airtight.

Inspect heat exchangers regularly, and clean more frequent- ly if the unit is located in a “dirty” environment. Keep the heat exchanger full of water at all times. Open loop systems should have an inverted P trap placed in the discharge line to keep water in the heat exchanger during off cycles. Closed loop systems must have a minimum of 105 kPa during the summer and 275 kPa during the winter.

Check P trap frequently for proper operation.

Table 15 — Aquazone™ D Control Current LED Status and Alarm Relay Operations

DESCRIPTION

STATUS LED

TEST LED

FAULT LED (Red)

ALARM RELAY

(Green)

(Yellow)

 

 

 

Normal Mode

On

Off

Flash Last Fault Code in Memory

Open

Normal Mode with PM

On

Off

Flashing Code 8

Cycle (closed 5 sec,

open 25 sec, …)

 

 

 

 

D Control is non-functional

Off

Off

Off

Open

Test Mode

On

Flash Last Fault Code in Memory

Cycling Appropriate Code

Night Setback

Flashing Code 2

Flash Last Fault Code in Memory

ESD

Flashing Code 3

Flash Last Fault Code in Memory

Invalid T-stat Inputs

Flashing Code 4

Flash Last Fault Code in Memory

No Fault in Memory

On

Off

Flashing Code 1

Open

HP Fault

Slow Flash

Off

Flashing Code 2

Open

LP Fault

Slow Flash

Off

Flashing Code 3

Open

FP1 Fault

Slow Flash

Off

Flashing Code 4

Open

FP2 Fault

Slow Flash

Off

Flashing Code 5

Open

CO Fault

Slow Flash

Off

Flashing Code 6

Open

Over/Under Voltage

Slow Flash

Off

Flashing Code 7

Open (closed after 15 minutes)

HP Lockout

Fast Flash

Off

Flashing Code 2

Closed

LP Lockout

Fast Flash

Off

Flashing Code 3

Closed

FP1 Lockout

Fast Flash

Off

Flashing Code 4

Closed

FP2 Lockout

Fast Flash

Off

Flashing Code 5

Closed

CO Lockout

Fast Flash

Off

Flashing Code 6

Closed

LEGEND

CO — Condensate Overflow

ESD — Emergency Shutdown

FP — Freeze Protection

HP — High Pressure

LP — Low Pressure

PM — Performance Monitor

NOTES:

1.If there is no fault in memory, the Fault LED will flash code 1.

2.Codes will be displayed with a 10-second Fault LED pause.

3.Slow flash is 1 flash every 2 seconds.

4.Fast flash is 2 flashes every 1 second.

5.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat contin- ually until the fault is cleared.

23

Page 23
Image 23
Carrier 50RHE006-060 specifications Service