Output EH2 will be off if FP1 is greater than 7.2 C and FP2 (when shorted) is greater than 43.3 C during Heating Stage 3 mode. This condition will have a
EMERGENCY HEAT — In Emergency Heat mode, the Fan Enable and Fan Speed relays are turned on. The EH1 output is turned on immediately. With continuing Emergency Heat de- mand, EH2 will turn on after 5 minutes. Fan Enable and Fan Speed relays are turned off after a
Output EH1, EH2, Fan Enable, and Fan Speed will be ON if the G input is not active during Emergency Heat mode.
COOLING STAGE 1 — In Cooling Stage 1 mode, the Fan Enable, compressor and RV relays are turned on immediately. If configured as stage 2 (DIP switch set to OFF) then the com- pressor and fan will not turn on until there is a stage 2 demand. The fan Enable and compressor relays are turned off immedi- ately when the Cooling Stage 1 demand is removed. The con- trol reverts to Standby mode. The RV relay remains on until there is a heating demand. If there is a master/slave or dual compressor application, all compressor relays and related func- tions will track with their associated DIP switch 2 on S1.
COOLING STAGE 2 — In Cooling Stage 2 mode, the Fan Enable, compressor and RV relays remain on. The Fan Speed relay is turned on immediately and turned off immediately once the Cooling Stage 2 demand is removed. The control re- verts to Cooling Stage 1 mode. If there is a master/slave or dual compressor application, all compressor relays and related func- tions will track with their associated DIP switch 2 on S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL staged Heating mode, the override (OVR) input becomes ac- tive and is recognized as a call for heating and the control will immediately go into a Heating Stage 1 mode. With an addition- al 30 minutes of NLL demand, the control will go into Heating Stage 2 mode. With another additional 30 minutes of NLL demand, the control will go into Heating Stage 3 mode.
SYSTEM TEST
System testing provides the ability to check the control operation. The control enters a
Test Mode — To enter Test mode on C or D controls, cycle the power 3 times within 60 seconds. The LED
NOTE: Deluxe D Control has a flashing code and alarm relay cycling code that will both have the same numerical label. For example, flashing code 1 will have an alarm relay cycling code 1. Code 1 indicates the control has not faulted since the last power off to power on sequence.
Table 13 — C Control Current LED Status
and Alarm Relay Operations
LED STATUS |
| DESCRIPTION OF OPERATION | ALARM RELAY | |
|
|
| Normal Mode | Open |
| On |
| Normal Mode with | Cycle |
|
| (closed 5 sec., | ||
|
|
| PM Warning | |
|
|
| Open 25 sec.) | |
|
|
|
| |
| Off |
| C Control is | Open |
Slow Flash |
| Fault Retry | Open | |
| Fast Flash |
| Lockout | Closed |
Slow Flash |
|
| Open | |
| Over/Under Voltage Shutdown | (Closed after | ||
|
|
|
| 15 minutes) |
Flashing Code 1 | Test Mode — No fault in memory | Cycling Code 1 | ||
Flashing Code 2 | Test Mode — HP Fault in memory | Cycling Code 2 | ||
Flashing Code 3 | Test Mode — LP Fault in memory | Cycling Code 3 | ||
Flashing Code 4 | Test Mode — FP1 Fault in memory | Cycling Code 4 | ||
Flashing Code 5 | Test Mode — FP2 Fault in memory | Cycling Code 5 | ||
Flashing Code 6 | Test Mode — CO Fault in memory | Cycling Code 6 | ||
Flashing Code 7 |
| Test Mode — Over/Under | Cycling Code 7 | |
| shutdown in memory | |||
|
|
|
| |
Flashing Code 8 |
| Test Mode — PM in memory | Cycling Code 8 | |
Flashing Code 9 |
| Test Mode — FP1/FP2 | Cycling Code 9 | |
| Swapped Fault in memory | |||
|
|
|
| |
| LEGEND |
|
| |
CO | — Condensate Overflow |
| ||
FP | — Freeze Protection |
| ||
HP | — High Pressure |
| ||
LED — |
| |||
LP | — Low Pressure |
| ||
PM | — Performance Monitor |
|
NOTES:
1.Slow flash is 1 flash every 2 seconds.
2.Fast flash is 2 flashes every 1 second.
3.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a
Table 14 — C Control LED Code and
Fault Descriptions
| LED | FAULT | DESCRIPTION | |
CODE | ||||
|
| |||
| 1 | No fault in memory | There has been no fault since | |
|
|
| the last | |
|
|
| sequence | |
| 2 | HP Open Instantly | ||
| 3 | LP open for 30 continuous sec- | ||
|
|
| onds before or during a call | |
|
|
| (bypassed for first 60 seconds) | |
| 4 | Freeze Protection Coax | FP1 below Temp limit for 30 con- | |
|
| — FP1 | tinuous seconds (bypassed for | |
|
|
| first 60 seconds of operation) | |
| 5 | Freeze Protection Air Coil | FP2 below Temp limit for 30 con- | |
|
| — FP2 | tinuous seconds (bypassed for | |
|
|
| first 60 seconds of operation) | |
| 6 | Condensate overflow | Sense overflow (grounded) for | |
|
|
| 30 continuous seconds | |
| 7 | Over/Under Voltage | "R" power supply is <19VAC or | |
(Autoreset) | Shutdown | >30VAC | ||
| 8 | PM Warning | Performance Monitor Warning | |
|
|
| has occurred. | |
| 9 | FP1 and FP2 Thermistors | FP1 temperature is higher than | |
|
| are swapped | FP2 in heating/test mode, or FP2 | |
|
|
| temperature is higher than FP1 | |
|
|
| in cooling/test mode. | |
| LEGEND |
| ||
FP | — Freeze Protection |
| ||
HP | — High Pressure |
| ||
LED — |
| |||
LP | — Low Pressure |
| ||
PM | — Performance Monitor |
|
22