Table 16 — Troubleshooting (cont)

FAULT

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Only Compressor Runs

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation.

 

X

X

Fan motor relay

Jumper G and R for fan operation. Check for line voltage across BR

 

 

 

 

contacts.

 

 

 

 

Check fan power enable relay operation (if present).

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

 

X

X

Thermostat wiring

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

operation in Test mode.

Unit Does Not Operate in

 

X

Reversing valve

Set for cooling demand and check 24 vac on RV coil and at control.

Cooling

 

 

 

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

 

 

operating, engage and disengage RV coil voltage to push valve.

 

 

X

Thermostat setup

Check for 'O' RV setup not 'B'.

 

 

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.

Insufficient Capacity/

X

X

Dirty filter

Replace or clean.

Not Cooling or Heating

 

 

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Properly

 

 

 

heating

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

External static too high. Check blower Table 4.

 

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

cooling

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

External static too high. Check blower Table 4.

 

X

X

Leaky ductwork

Check supply and return air temperatures at the unit and at distant duct

 

 

 

 

registers if significantly different, duct leaks are present.

 

X

X

Low refrigerant charge

Check superheat and subcooling Table 9.

 

X

X

Restricted metering device

Check superheat and subcooling Table 9. Replace.

 

 

X

Defective reversing valve

Perform RV touch test.

 

X

X

Thermostat improperly

Check location and for air drafts behind thermostat.

 

 

 

located

 

 

X

X

Unit undersized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

capacity.

 

X

X

Scaling in water heat

Perform scaling check and clean if necessary.

 

 

 

exchanger

 

 

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

heating

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

External static too high. Check blower Table 4.

 

 

X

Reduced or no water flow in

Check pump operation or valve operation/setting.

 

 

 

cooling

Check water flow; adjust to proper flow rate. See Table 8.

 

 

 

 

 

 

X

Inlet water too hot

Check load, loop sizing, loop backfill, ground moisture.

 

X

 

Air temperature out of range

Bring return air temperature within design parameters.

 

 

 

in heating

 

 

 

X

Scaling in water heat

Perform scaling check and clean if necessary.

 

 

 

exchanger

 

 

X

X

Unit overcharged

Check superheat and subcooling. Reweigh in charge.

 

X

X

Non-condensables in

Vacuum system and reweigh in charge.

 

 

 

system

 

 

X

X

Restricted metering device

Check superheat and subcooling per Table 9. Replace.

Low Suction Pressure

X

 

Reduced water flow in

Check pump operation or water valve operation/setting.

 

 

 

heating

Plugged strainer or filter. Clean or replace.

 

 

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

X

 

Water temperature out of

Bring water temperature within design parameters.

 

 

 

range

 

 

 

X

Reduced airflow in cooling

Check for dirty air filter and clean or replace.

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

External static too high. Check blower Table 4.

 

 

X

Air temperature out of range

Too much cold vent air. Bring entering air temperature within design

 

 

 

 

parameters.

 

X

X

Insufficient charge

Check for refrigerant leaks.

Low Discharge Air

X

 

Too high airflow

Check blower Table 4.

Temperature in Heating

X

 

Poor performance

See 'Insufficient Capacity'.

High Humidity

 

X

Too high airflow

Check blower Table 4.

 

 

X

Unit oversized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

capacity.

LEGEND

 

 

 

 

RV — Reversing Valve

 

 

 

 

27

Page 27
Image 27
Carrier 50RHE006-060 specifications Unit Does Not Operate

50RHE006-060 specifications

The Carrier 50RHE006-060 is a robust commercial rooftop unit designed for efficient heating and cooling in various applications. This model is part of Carrier’s renowned line of HVAC systems, known for their reliability and performance. With a nominal cooling capacity of 5 tons and heating capacity of 6 tons, this unit is suitable for medium-sized commercial spaces such as retail stores, offices, and schools.

One of the standout features of the Carrier 50RHE006-060 is its advanced scroll compressor technology. This type of compressor is recognized for its efficiency and durability, offering quiet operation while minimizing energy consumption. The inclusion of a variable-speed blower motor enhances comfort by providing consistent airflow while also reducing energy costs by adjusting the speed according to the demand.

Another key characteristic is its integrated microprocessor control system, which allows for precise temperature management. This feature not only provides optimal comfort but also ensures energy savings. The system’s controls can be easily integrated with existing building management systems, allowing for seamless operation and monitoring.

The Carrier 50RHE006-060 boasts enhanced insulation properties, which help reduce noise during operation and improve energy efficiency. Its robust design can withstand various weather conditions, making it a reliable choice for rooftop installation. Moreover, it is designed with accessibility in mind, featuring service doors that allow for easy maintenance, reducing downtime and operational costs.

In terms of efficiency, the unit is designed to meet or exceed EPA energy efficiency standards. It utilizes environmentally friendly refrigerants, adhering to regulations aimed at reducing greenhouse gas emissions. Additionally, the design includes a high-efficiency heat exchanger, which maximizes heat transfer and improves overall performance.

The Carrier 50RHE006-060 is also equipped with a dual-stage heat function, allowing it to provide optimal heating for varying weather conditions, ensuring comfort during the colder months. Furthermore, the unit’s design incorporates features such as hot gas bypass for improved dehumidification, making it adaptable to different climates and enhancing indoor air quality.

In summary, the Carrier 50RHE006-060 stands out with its efficient compressor technology, smart control systems, robust construction, and environmentally conscious design. These features make it a top choice for commercial spaces seeking an effective, reliable, and energy-efficient heating and cooling solution.