Carrier 50RHE006-060 Electrical Data, 50RHE Typical Single-PhaseLine, Voltage Power Connection

Models: 50RHE006-060

1 32
Download 32 pages 52.62 Kb
Page 14
Image 14
Table 3 — Electrical Data

Table 3 — Electrical Data

50RHE

VOLTS-PHASE

VOLTAGE

COMPRESSOR

FAN

TOTAL

MIN

MAX

 

 

MOTOR

UNIT

CIRCUIT

UNIT

(50 Hz)

MIN/MAX

RLA

LRA

FUSE/HACR

FLA

FLA

AMP

 

 

 

 

 

 

 

006

 

220/240-1

197/254

2.3

15.0

0.4

2.7

3.2

15

 

 

 

 

 

 

 

 

 

 

009

 

220/240-1

197/254

2.7

18.8

0.7

3.7

4.5

15

 

 

 

 

 

 

 

 

 

 

012

 

220/240-1

197/254

3.9

22.2

0.7

4.5

5.6

15

 

 

 

 

 

 

 

 

 

 

015

 

220/240-1

197/254

4.2

27.0

0.9

5.9

7.1

15

 

 

 

 

 

 

 

 

 

 

019

 

220/240-1

197/254

6.8

45.0

0.9

8.6

10.5

15

 

 

 

 

 

 

 

 

 

 

024

 

220/240-1

197/254

8.2

51.0

1.6

10.4

12.6

20

 

 

 

 

 

 

 

 

 

 

030

 

220/240-1

197/254

9.1

54.0

1.7

11.2

13.6

20

 

 

 

 

 

 

 

 

 

 

380-415-3

342/462

3.3

25.0

1.0

4.3

5.2

15

 

 

 

 

 

 

 

 

 

 

 

 

036

 

220/240-1

197/254

11.5

83.0

2.7

17.2

20.8

35

 

 

 

 

 

 

 

 

 

 

380-415-3

342/462

4.2

32.0

1.7

5.9

6.9

15

 

 

 

 

 

 

 

 

 

 

 

 

042

 

380-415-3

342/462

5.5

34.5

1.7

6.0

7.1

15

 

 

 

 

 

 

 

 

 

 

048

 

380-415-3

342/462

5.9

42.0

1.8

7.5

8.9

15

 

 

 

 

 

 

 

 

 

 

060

 

380-415-3

342/462

8.2

61.8

2.5

9.9

11.8

15

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

FLA

Full Load Amps

 

 

 

 

 

 

 

HACR — Heating, Air Conditioning and Refrigeration

 

 

 

 

 

 

LRA — Locked Rotor Amps

 

 

 

 

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

 

 

POWER CONNECTION — Make line voltage connection by connecting the incoming line voltage wires to the L side of the CC terminal as shown in Fig. 13. See Table 3 for correct wire and maximum overcurrent protection sizing.

SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.

On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter- mine the percentage voltage imbalance:

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 volts

BC = 464 volts

AC = 455 volts

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v. Determine percent voltage imbalance.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.

NOTE: If more than 2% voltage imbalance is present, contact local electric utility.

220-VOLT OPERATION — All 220-240 volt units are factory wired for 208 volts. The transformers may be switched to 220-volt operation by switching the red (220 volt) wire with the orange (240 volt) wire at the TB1-1 terminal for single- phase and TB1-3 for 3-phase.

% Voltage Imbalance = 100 x

7

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Fig. 13 — 50RHE Typical Single-Phase Line

Voltage Power Connection

14

Page 14
Image 14
Carrier 50RHE006-060 specifications Electrical Data, 50RHE Typical Single-PhaseLine, Voltage Power Connection