Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 7 for additional information.
Lifting holes are provided in base rails as shown in Fig. 7. Refer to rigging instructions on unit.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck.
Before setting the unit onto the curb, recheck gasketing on curb.
Positioning on Curb —
Position unit on roof curb so that the following clearances are maintained: 6.4 mm (1/4 in.) clearance between the roof curb and the base rail inside the front and back,
0.0mm (0.0 in.). clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately equal to section
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
After unit is in position, remove rigging skids and shipping materials.
Step 7 — Convert to Horizontal and Connect Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
C06108
Fig. 8 - Horizontal Conversion Panels
Step 8 — Install Outside Air Hood
Economizer Hood Removal and Setup - Factory Option
1.The hood is shipped in
2.To gain access to the hood, remove the filter access panel. (See Fig. 9.)
3.Locate and cut the (2) plastic
4.Carefully lift the hood assembly through the filter access opening and assemble per the steps outlined in Economizer Hood and