5.Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 14.
DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
ALUMINUM FILTER FILTER
BAROMETRIC RELIEF
FILTER CLIP
C08634
Fig. 14 - Economizer Filter Installation
6.Caulk the ends of the joint between the unit top panel and the hood top.
7.Replace the filter access panel.
Step 9 — Install External Condensate Trap and Line
The unit has one 19 mm
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a 12.7 mm
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a 12 mm
CONDENSATE PAN (SIDE VIEW) |
| ALTERNATE | ||
STANDARD | DRAIN PLUG | |||
BOTTOM DRAIN | ||||
SIDE DRAIN | ||||
|
|
C08021
Fig. 15 - Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 16.
MINIMUM PITCH |
|
|
25 mm (1 in.) PER | BASE RAIL |
|
3m (10 ft.) OF LINE |
|
|
|
| 51 mm |
| OPEN | (2 in.) |
| MIN | |
| VENT | |
|
| |
TO ROOF |
| SEE NOTE |
DRAIN |
| |
|
| |
|
| ROOF |
|
| CURB |
| DRAIN PLUG |
NOTE: Trap should be deep enough to offset maximum unit static |
| |
difference. A 102 mm (4 in.) trap is recommended. | 50TC | |
C09387 | ||
| ||
Fig. 16 - Condensate Drain Piping Details |
|
All units must have an external trap for condensate drainage. Install a trap at least 102 mm
Step 10 — Make Electrical Connections
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with local electrical codes or in absence of local codes, it is recommended that the U.S.A. standard ANSI/NFPA 70, National Electrical Code (NEC), be followed.
NOTE: Check all factory and field electrical connections for tightness.
Field power wires are connected to the unit at
NOTE: Make field power connections directly to line connection pressure lugs only.
13