Carrier 50TC Indoor/Outdoor Air Quality CO2 Sensor, 33ZCSENCO2 - Typical Wiring Diagram

Models: 50TC

1 40
Download 40 pages 24.16 Kb
Page 24
Image 24
Fig. 37 - Indoor/Outdoor Air Quality (CO2) Sensor

50TC

H G 24 VAC OR

+ - 24 VDC

+ 0-10VDC

- SIG COM + 4-20mA

NC }ALARM

COM RELAY

NO CONTACTS

2 1 8 7 6 5 4 3 2 1

J3 J4

C08635

Refer to Form 33CS-58SI, PremierLink Installation, Start-up, and Configuration Instructions, for detailed configuration information

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) — The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 39. The outdoor air CO2 sensor must be located in the economizer outside air hood.

Fig. 37 - Indoor/Outdoor Air Quality (CO2) Sensor

(33ZCSENCO2) - Typical Wiring Diagram

To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 0.9 m (3 ft) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor —

For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 37. Connect the 4-20 mA terminal to terminal TB1-9 and connect the SIG COM terminal to terminal TB1-11. See Fig. 38.

IAQ Sensor

TB1PL SEN (33ZCSENCO2) - Typical Wiring Diagram 9 Fig. 38 - Indoor CO2 Sensor (33ZCSENCO2)Fig. 39 - Outdoor Air Quality Sensor Cover J5-5

TB1

COM Fig. 40 - Outdoor CO2 Sensor Connections11Manual backgroundManual background J5-3

24 VAC

C08636

Fig. 38 - Indoor CO2 Sensor (33ZCSENCO2)

Connections

COVER REMOVED

SIDE VIEW

C07135

Fig. 39 - Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO2 Sensor — A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 37. Connect the 4 to 20 mA terminal to the TB1-13 terminal of the 50TC. Connect the SIG COM terminal to the TB1-11 terminal of the 50TC. See Fig. 40.

OAQ Sensor/RH Sensor

TB1PL SEN Manual background13 Manual backgroundManual background J5-2

TB1

COM Manual background11Manual backgroundManual background J5-3

24 VAC

C08275

Fig. 40 - Outdoor CO2 Sensor Connections

Fire Shutdown (FSD) — This function is available only when PremierLink is configured for (Space) Sensor Mode. The unit is factory-wired for PremierLink FSD operation when PremierLink is factory-installed.

Filter Status Switch — This function is available only when PremierLink is configured for (Space) Sensor Mode.

24

Page 24
Image 24
Carrier 50TC Indoor/Outdoor Air Quality CO2 Sensor, 33ZCSENCO2 - Typical Wiring Diagram, Indoor CO2 Sensor 33ZCSENCO2