Carrier 50TC Field Fabricate Ductwork, Unit Leveling Tolerances, Rigging Details, Detail A, Side

Models: 50TC

1 40
Download 40 pages 24.16 Kb
Page 10
Image 10
Fig. 6 - Unit Leveling Tolerances

MAXIMUM ALLOWABLE

DIFFERENCE IN. (MM)

A-B

B-C

A-C

0.5” (13)

1.0” (25)

1.0” (25)

C06110

Fig. 6 - Unit Leveling Tolerances

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition) shall not exceed 87 Pa (0.35 in. wg) with economizer or 112 Pa (0.45 in. wg) without economizer.

For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.

Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

For units with accessory electric heaters: Horizontal applications require a minimum clearance to combustible surfaces of 25 mm (1-in) from duct for first 305 mm (12-in) away from unit. Vertical applications do not require a minimum clearance.

Minimum clearance is not required around ductwork.

50TC

 

 

PLACE ALL SEAL STRIP

DETAIL A

“B”

914-1371

IN PLACE BEFORE PLACING

UNIT ON ROOF CURB

 

 

(36"-54")

 

 

 

 

 

 

DUCT END

 

 

“C”

SEE DETAIL “A”

 

 

 

 

FAN

 

 

 

SIDE

“A”

 

 

 

 

 

 

 

 

C09458

 

MAX WEIGHT

 

 

 

DIMENSIONS

 

 

 

UNIT

 

A

 

B

 

C

 

 

 

 

 

 

KG

LB

MM

 

IN

MM

 

IN

MM

 

IN

50TC-A07

336

740

1890

 

74.5

965

 

38.0

850

 

33.5

 

 

 

 

 

 

 

 

 

 

 

 

50TC-D08

641

1410

2235

 

88.0

1040

 

41.0

1055

 

41.5

 

 

 

 

 

 

 

 

 

 

 

 

50TC-D09

693

1525

2235

 

88.0

1030

 

40.5

1255

 

49.5

 

 

 

 

 

 

 

 

 

 

 

 

50TC-D12

711

1565

2235

 

88.0

1015

 

40.0

1255

 

49.5

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Dimensions in ( ) are in inches.

2.Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.

Fig. 7 - Rigging Details

10