50TC

Table 9 – RTU-MP Controller Inputs and Outputs

 

 

POINT NAME

BACnet OBJECT

 

TYPE OF I/O

CONNECTION PIN

 

 

NAME

 

NUMBERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUTS

 

 

Space Temperature Sensor

sptsens

 

AI (10K Thermistor)

J20---1, 2

 

 

 

 

 

Supply Air Temperature

sat

 

AI (10K Thermistor)

J2---1, 2

 

 

 

 

 

Local Outside Air Temperature Sensor

oatsens

 

AI (10K Thermistor)

J2---3, 4

Space Temperature Offset Pot

sptopot

 

AI (100K Potentiometer)

J20---3

 

 

 

 

 

Indoor Air Quality

iaq

 

AI (4---20 ma)

J4---2, 3

 

 

 

 

 

Outdoor Air Quality

oaq

 

AI (4---20 ma)

J4---5, 6

Safety Chain Feedback

safety

 

DI (24 VAC)

J1---9

Compressor Safety

compstat

 

DI (24 VAC)

J1---2

 

 

 

 

 

Fire Shutdown

firedown

 

DI (24 VAC)

J1---10

 

 

 

 

 

Enthalpy Switch

enthalpy

 

DI (24 VAC)

J2---6, 7

Humidistat Input Status

humstat

 

DI (24 VAC)

J5---7, 8

 

 

 

CONFIGURABLE

INPUTS*

 

Space Relative Humidity

sprh

 

AI (4---20 ma)

J4---2,3 or J4---5,6

 

 

 

 

 

 

Outside Air Relative Humidity

oarh

 

AI (4---20 ma)

 

 

 

 

 

 

 

Supply Fan Status

fanstat

 

DI (24 VAC)

J5---1,2 or J5---3,4 or

 

 

 

 

 

 

Filter Status

filtstat

 

DI (24 VAC)

 

J5 5,6 or J5---7,8

 

 

 

 

 

 

Remote Occupancy Input

remocc

 

DI (24 VAC)

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUTS

 

 

 

Economizer Commanded Position

econocmd

 

4---20ma

J2---5

 

 

 

 

 

Supply Fan Relay State

sf

 

DO Relay (24VAC , 1A)

J1---4

Compressor 1 Relay State

comp_1

 

DO Relay (24VAC , 1A)

J1---8

Compressor 2 Relay State

comp_2

 

DO Relay (24VAC , 1A)

J1---7

 

 

 

 

 

Heat Stage 1 Relay State

heat_1

 

DO Relay (24VAC , 1A)

J1---6

 

 

 

 

 

Heat Stage 2 Relay State

heat_2

 

DO Relay (24VAC , 1A)

J1---5

Power Exhaust Relay State

aux_2

 

DO Relay (24VAC , 1A)

J11---3

 

 

 

 

 

Dehumidification Relay State

humizer

 

DO Relay (24VAC, 1A)

J11---7, 8

LEGEND

 

 

 

 

AI

---

Analog Input

 

 

 

 

AO ---

Analog Output

 

 

 

 

DI

---

Discrete Input

 

 

 

 

DO ---

Discrete Output

 

 

 

 

*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field--- installation.

The RTU-MP controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU-MP system.

Supply Air Temperature (SAT) Sensor - On FIOP-equipped 50TC unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 152 mm (6-inches) in length. It is a nominal 10-k ohm thermistor.

The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 12.7 m (1/2-in.) hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 28.

Outdoor Air Temperature (OAT) Sensor - The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.

EconoMi$er2 - The RTU-MP control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU-MP control; EconoMi$er2 has no internal logic device.

Outdoor air management functions can be enhanced with field-installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors) Space CO2 sensor

Outdoor air CO2 sensor

29

Page 29
Image 29
Carrier 50TC installation instructions RTU-MP Controller Inputs and Outputs, Type of I/O Connection PIN Name Numbers Inputs

50TC specifications

The Carrier 50TC is a cutting-edge commercial rooftop unit designed for optimal performance and reliability in a variety of HVAC applications. This unit is particularly well-suited for small to medium-sized facilities that require efficient heating, ventilation, and air conditioning solutions. A hallmark of the Carrier 50TC is its impressive energy efficiency, enabling users to significantly lower their operational costs while maintaining a comfortable indoor environment.

One of the standout features of the Carrier 50TC is its advanced performance technologies. The unit employs a high-efficiency scroll compressor that enhances refrigerant management, allowing for exceptional cooling capacities while minimizing energy consumption. Additionally, the unit is equipped with variable speed fans, which further contribute to its operational efficiency. These fans adjust their speed according to the cooling demands, allowing the system to consume energy only when necessary.

The Carrier 50TC also incorporates an innovative control system that provides intelligent diagnostics and an array of customizable settings. This system helps in monitoring the unit's performance, ensuring maximum efficiency and early detection of potential maintenance issues. Users can easily integrate the unit within their existing building management systems, enhancing overall operational control and streamlining HVAC management procedures.

Durability and ease of maintenance are key characteristics of the Carrier 50TC, designed specifically to withstand harsh weather conditions while providing long-lasting performance. The unit's robust construction includes a powder-coated cabinet, which not only improves its aesthetic appeal but also protects against corrosion, ensuring longevity.

Moreover, the Carrier 50TC is designed with eco-friendliness in mind. It utilizes environmentally friendly refrigerants, aligning with modern regulations aimed at reducing the impact of HVAC systems on the environment. By choosing the Carrier 50TC, businesses can contribute to sustainability efforts while enjoying effective temperature control.

In summary, the Carrier 50TC combines energy efficiency, advanced technologies, and robust design to deliver a reliable HVAC solution for commercial applications. With its smart control system, high-efficiency components, and eco-friendly operation, the Carrier 50TC sets a standard for performance and sustainability in the commercial heating and cooling market.