PremierLinkt (Factory-Option) —
50TC
C08199
Fig. 27 - PremierLink Controller
The PremierLink controller (see Fig. 27) is compatible with Carrier Comfort Networkr (CCN) devices. This control is designed to allow users the access and ability to change
The PremierLink control is
The PremierLink controller requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied).
NOTE: PremierLink controller is shipped in Sensor mode. To be used with a thermostat, the PremierLink controller must be configured to Thermostat mode. Refer to PremierLink Configuration instructions for Operating Mode.
Supply Air Temperature (SAT) Sensor — On
The SAT is
SUPPLY AIR | ROOF |
TEMPERATURE | CURB |
SENSOR | RETURN AIR |
SUPPLY AIR | |
| C09059 |
Fig. 28 - Typical Mounting Location for Supply Air Temperature (SAT) Sensor on Small Rooftop Units
NOTE: Refer to Form
NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit’s heater surfaces.
18