Carrier 50TC installation instructions LEDs

Models: 50TC

1 40
Download 40 pages 24.16 Kb
Page 34
Image 34
Table 10 – LEDs

 

 

Table 10 – LEDs

 

The LEDs on the RTU-MP show the status of certain functions

 

 

 

If this LED is on...

 

Status is...

 

 

 

Power

 

The RTU MP has power

 

 

 

Rx

 

The RTU MP is receiving data from the network segment

 

 

The RTU MP is transmitting data over the network segment

Tx

 

 

 

The digital output is active

DO#

 

 

 

 

 

The Run and Error LEDs indicate control module and network status

50TC

If Run LED shows...

And Error LED shows...

2 flashes per second

Off

 

 

2 flashes per second

2 flashes,

alternating with Run LED

 

2 flashes per second

3 flashes,

then off

 

2 flashes per second

4 flashes,

then pause

 

 

 

2 flashes per second

On

 

 

5 flashes per second

On

 

 

5 flashes per second

Off

 

 

7 flashes per second

7 flashes per second, alternating with

Run LED

 

 

 

14 flashes per second

14 flashes per second,

alternating with Run LED

 

 

 

On

On

 

 

Status is...

Normal

Five minute auto---restart delay after system error

Control module has just been formatted

Two or more devices on this network have the same ARC156 network address

Exec halted after frequent system errors or control programs halted

Exec start---up aborted, Boot is running Firmware transfer in progress, Boot is running

Ten second recovery period after brownout

Brownout

Failure. Try the following solutions:

STurn the RTU---MP off, then on. S Format the RTU---MP.

S Download memory to the RTU---MP. S Replace the RTU---MP.

NOTE: Refer to Form 48-50H-T-2T for complete configuration of RTU-MP, operating sequences and troubleshooting information. Refer to RTU-MP 3rd Party Integration Guide for details on configuration and troubleshooting of connected networks. Have a copy of these manuals available at unit start-up.

34

Page 34
Image 34
Carrier 50TC installation instructions LEDs