Carrier 58MVP instruction manual Step

Models: 58MVP

1 48
Download 48 pages 27.19 Kb
Page 10
Image 10

NOT ENOUGH COOLING AIRFLOWÐGenerally, this indicates the Y/Y2 thermostat lead is not properly connected.

STEP

ACTION

YES

NO

GO TO

1.

Remove blower access panel and depress door switch. Use a piece of tape to hold switch closed.

Ð

Ð

2

Wait a few sec for self test before proceeding to next step.

 

 

 

 

2.

Make sure thermostat is calling for cooling. If thermostat lead G is not connected, jumper across

Ð

Ð

3

thermostat terminals R and G.

 

 

 

 

3.

Make sure thermostat fan control is in AUTO position if equipped.

Ð

Ð

4

4.

Do you have 24v across Y/Y2 and Com on furnace control board?

8

5

Ð

5.

You have a defective thermostat, or a break in wiring between thermostat and furnace, or the Y/Y2

Ð

Ð

6

thermostat terminal is not wired to thermostat.

 

 

 

 

6.

Fix problem.

Ð

Ð

7

7.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

Ð

Ð

INDEX

8.

Are air conditioning select switches A/C set to proper tonnage as required by condensing unit? (See

10

9

Ð

Table 1.)

 

 

 

 

9.

Set air conditioning select switches A/C for proper tonnage as required by condensing unit. (See

Ð

Ð

7

Table 1.)

 

 

 

 

10.

Disconnect the G thermostat lead or jumper if used.

Ð

Ð

11

11.

Does blower motor turn off in 90 sec when G thermostat lead is disconnected?

12

13

Ð

12.

Replace furnace control board.

Ð

Ð

7

13.

Observe operation of furnace in cooling mode for 8 minutes.

Ð

Ð

14

14.

Does furnace operate properly in cooling mode?

15

16

Ð

 

Make sure outdoor unit is properly charged. If it is, go to page number indicated in Index for

 

 

 

15.

CLEANUP AND START-UP INSTRUCTIONS. If problem persists on an intermittent basis, replace

Ð

Ð

INDEX

furnace control board. If problem still persists after replacing furnace control board, contact your dis-

 

 

 

 

 

tributor.

 

 

 

 

 

 

 

 

16.

Does furnace abruptly go through a self-test sequence as blower comes up to speed?

17

24

Ð

17.

Do you have less than 17 vac between R and Com on furnace control board?

18

24

Ð

18.

Do you have less than 90 vac between P1 and P2 on furnace control board?

19

20

Ð

19.

Make sure the wire gage between main fuse box and furnace complies with wire size specification

Ð

Ð

6

in Installation, Start-Up, and Operating Instructions.

 

 

 

 

 

 

 

 

 

20.

Disconnect the R thermostat lead.

Ð

Ð

21

 

 

 

 

 

21.

Do you have less than 17 vac between R and Com on furnace control board?

22

23

Ð

 

 

 

 

 

22.

Replace transformer.

Ð

Ð

7

23.

Check the thermostat wire gage between furnace and thermostat, and furnace and outdoor unit. It is

 

 

 

recommended that AWG No. 18 color-coded copper thermostat wire be used for lengths up to 100

Ð

Ð

6

 

ft. For wire lengths over 100 ft, use AWG No. 16 wire.

 

 

 

24.

Press down on microprocessor chip and make sure it is properly seated to furnace control board. If

Ð

Ð

6

it is, replace furnace control board.

 

 

 

 

 

 

 

 

 

Table 1ÐAir Conditioning (A/C) Airflow Setup Switch Position

AIR CONDITIONER

AIRFLOW

A/C SWITCH POSITION

 

ALLOWABLE FURNACE MODEL SETUP

 

 

(TONS)

(CFM)

A/C-1

A/C-2

A/C-3

040

060

080

 

080

 

100

 

120

Default

1200 or

OFF

OFF

OFF

3 Tons

3 Tons

3 Tons

5

Tons

5

Tons

5

Tons

2000

1200 CFM

1200 CFM

1200 CFM

2000 CFM

2000 CFM

2000 CFM

 

 

 

 

1-1/2

600

ON

OFF

OFF

X

X

X

 

Ð

 

Ð

Ð

 

2

800

OFF

ON

OFF

X

X

X

 

X

 

X

 

X

2-1/2

1000

ON

ON

OFF

X

X

X

 

X

 

X

 

X

3

1200

OFF

OFF

ON

X

X

X

 

X

 

X

 

X

3-1/2

1400

ON

OFF

ON

X

X

X

 

X

 

X

 

X

4

1600

OFF

ON

ON

Ð

Ð

Ð

X

 

X

 

X

 

5

2000

ON

ON

ON

Ð

Ð

Ð

X

 

X

 

X

 

XÐIndicates allowable selection.

10

Page 10
Image 10
Carrier 58MVP instruction manual Step