NOT ENOUGH COOLING AIRFLOWÐGenerally, this indicates the Y/Y2 thermostat lead is not properly connected.
STEP | ACTION | YES | NO | GO TO | |
1. | Remove blower access panel and depress door switch. Use a piece of tape to hold switch closed. | Ð | Ð | 2 | |
Wait a few sec for self test before proceeding to next step. | |||||
|
|
|
| ||
2. | Make sure thermostat is calling for cooling. If thermostat lead G is not connected, jumper across | Ð | Ð | 3 | |
thermostat terminals R and G. | |||||
|
|
|
| ||
3. | Make sure thermostat fan control is in AUTO position if equipped. | Ð | Ð | 4 | |
4. | Do you have 24v across Y/Y2 and Com on furnace control board? | 8 | 5 | Ð | |
5. | You have a defective thermostat, or a break in wiring between thermostat and furnace, or the Y/Y2 | Ð | Ð | 6 | |
thermostat terminal is not wired to thermostat. | |||||
|
|
|
| ||
6. | Fix problem. | Ð | Ð | 7 | |
7. | Go to page number indicated in Index for CLEANUP AND | Ð | Ð | INDEX | |
8. | Are air conditioning select switches A/C set to proper tonnage as required by condensing unit? (See | 10 | 9 | Ð | |
Table 1.) | |||||
|
|
|
| ||
9. | Set air conditioning select switches A/C for proper tonnage as required by condensing unit. (See | Ð | Ð | 7 | |
Table 1.) | |||||
|
|
|
| ||
10. | Disconnect the G thermostat lead or jumper if used. | Ð | Ð | 11 | |
11. | Does blower motor turn off in 90 sec when G thermostat lead is disconnected? | 12 | 13 | Ð | |
12. | Replace furnace control board. | Ð | Ð | 7 | |
13. | Observe operation of furnace in cooling mode for 8 minutes. | Ð | Ð | 14 | |
14. | Does furnace operate properly in cooling mode? | 15 | 16 | Ð | |
| Make sure outdoor unit is properly charged. If it is, go to page number indicated in Index for |
|
|
| |
15. | CLEANUP AND | Ð | Ð | INDEX | |
furnace control board. If problem still persists after replacing furnace control board, contact your dis- | |||||
|
|
|
| ||
| tributor. |
|
|
| |
|
|
|
|
| |
16. | Does furnace abruptly go through a | 17 | 24 | Ð | |
17. | Do you have less than 17 vac between R and Com on furnace control board? | 18 | 24 | Ð | |
18. | Do you have less than 90 vac between P1 and P2 on furnace control board? | 19 | 20 | Ð | |
19. | Make sure the wire gage between main fuse box and furnace complies with wire size specification | Ð | Ð | 6 | |
in Installation, | |||||
|
|
|
| ||
|
|
|
|
| |
20. | Disconnect the R thermostat lead. | Ð | Ð | 21 | |
|
|
|
|
| |
21. | Do you have less than 17 vac between R and Com on furnace control board? | 22 | 23 | Ð | |
|
|
|
|
| |
22. | Replace transformer. | Ð | Ð | 7 | |
23. | Check the thermostat wire gage between furnace and thermostat, and furnace and outdoor unit. It is |
|
|
| |
recommended that AWG No. 18 | Ð | Ð | 6 | ||
| ft. For wire lengths over 100 ft, use AWG No. 16 wire. |
|
|
| |
24. | Press down on microprocessor chip and make sure it is properly seated to furnace control board. If | Ð | Ð | 6 | |
it is, replace furnace control board. | |||||
|
|
|
| ||
|
|
|
|
|
Table 1ÐAir Conditioning (A/C) Airflow Setup Switch Position
AIR CONDITIONER | AIRFLOW | A/C SWITCH POSITION |
| ALLOWABLE FURNACE MODEL SETUP |
|
| ||||||||
(TONS) | (CFM) | 040 | 060 | 080 |
| 080 |
| 100 |
| 120 | ||||
Default | 1200 or | OFF | OFF | OFF | 3 Tons | 3 Tons | 3 Tons | 5 | Tons | 5 | Tons | 5 | Tons | |
2000 | 1200 CFM | 1200 CFM | 1200 CFM | 2000 CFM | 2000 CFM | 2000 CFM | ||||||||
|
|
|
| |||||||||||
600 | ON | OFF | OFF | X | X | X |
| Ð |
| Ð | Ð |
| ||
2 | 800 | OFF | ON | OFF | X | X | X |
| X |
| X |
| X | |
1000 | ON | ON | OFF | X | X | X |
| X |
| X |
| X | ||
3 | 1200 | OFF | OFF | ON | X | X | X |
| X |
| X |
| X | |
1400 | ON | OFF | ON | X | X | X |
| X |
| X |
| X | ||
4 | 1600 | OFF | ON | ON | Ð | Ð | Ð | X |
| X |
| X |
| |
5 | 2000 | ON | ON | ON | Ð | Ð | Ð | X |
| X |
| X |
|
XÐIndicates allowable selection.
10