25. | Connect 1 side of a slope manometer with a tee to collector box pressure tap. Connect other side | Ð | Ð | 26 | |
with a tee to gas valve air pressure fitting. Refer to pressure check diagram in Appendix C. | |||||
|
|
|
| ||
|
|
|
|
| |
26. | Turn power on and wait several sec, then jumper R and W/W1 thermostat terminals on furnace con- | Ð | Ð | 27 | |
trol board. | |||||
|
|
|
| ||
27. | Monitor slope manometer. Does pressure reading appear to be stable when fault occurs? | 14 | 28 | Ð | |
28. | Check for a sag in vent pipe. If problem persists, replace inducer motor. | Ð | Ð | 8 | |
29. | Disconnect jumper wire across R and W/W1 thermostat terminals and wait until blower stops. | Ð | Ð | 30 | |
30. | Jumper R, W/W1, and W2 thermostat terminals on furnace control board. | Ð | Ð | 31 | |
31. | Does | 32 | 33 | Ð | |
32. | The problem is either a sag in vent pipe or a clogged drain trap or line. | Ð | Ð | 17 | |
33. | Does fault occur before main burners ignite? | 34 | 51 | Ð | |
34. | Do you have 24v between C (Common) on | 36 | 35 | Ð | |
board? | |||||
|
|
|
| ||
35. | The YELLOW wire to | Ð | Ð | 8 | |
it. | |||||
|
|
|
| ||
| Do you have at least 1.90 in. wc pressure drop across heat exchangers when fault occurs? Deter- |
|
|
| |
36. | mine this by connecting 1 side of slope manometer with a tee to collector box pressure tap. Con- | 45 | 37 | Ð | |
nect other side with a tee to gas valve air pressure fitting. Refer to pressure check diagram in Ap- | |||||
|
|
|
| ||
| pendix C. |
|
|
| |
37. | Is inducer motor MTR1 rotating in direction indicated on inducer housing? | 39 | 38 | Ð | |
38. | Replace inducer motor or inducer motor assembly. | Ð | Ð | 8 | |
39. | Turn power off. | Ð | Ð | 40 | |
40. | Is inducer wheel okay? | 42 | 41 | Ð | |
41. | If possible, replace inducer wheel. Otherwise, replace inducer motor assembly. | Ð | Ð | 8 | |
42. | Is there any frost | 43 | 44 | Ð | |
43. | The problem is caused by reversed vent and | Ð | Ð | 17 | |
|
|
|
| ||
44. | You have excessive restriction in | Ð | Ð | 8 | |
45. | Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. | Ð | Ð | 46 | |
46. | Turn power on and wait several sec, then jumper R, W/W1, and W2 thermostat terminals on fur- | Ð | Ð | 47 | |
nace control board. | |||||
|
|
|
| ||
47. | Do you have 24v between connector terminal | 11 | 48 | Ð | |
occurs? | |||||
|
|
|
| ||
|
|
|
|
| |
48. | Turn power off. | Ð | Ð | 49 | |
|
|
|
|
| |
49. | Do you have continuity across terminal | 14 | 50 | Ð | |
switch HPS? | |||||
|
|
|
| ||
|
|
|
|
| |
50. | The BROWN wire from | Ð | Ð | 8 | |
nection. Repair wire or replace harness. | |||||
|
|
|
| ||
|
|
|
|
| |
51. | Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. | Ð | Ð | 52 | |
|
|
|
|
| |
52. | Connect 1 side of a slope manometer with a tee to collector box pressure tap. Connect other side | Ð | Ð | 53 | |
with a tee to gas valve air pressure fitting. Refer to pressure check diagram in Appendix C. | |||||
|
|
|
| ||
|
|
|
|
| |
53. | Turn power on and wait several sec, then jumper R, W/W1, and W2 thermostat terminals on fur- | Ð | Ð | 54 | |
nace control board. | |||||
|
|
|
| ||
|
|
|
|
| |
54. | Monitor slope manometer. Does pressure reading appear to be stable when fault occurs? | 55 | 56 | Ð | |
|
|
|
|
| |
55. | Replace pressure switch assembly. If problem persists, check wiring for an intermittent connection | Ð | Ð | 8 | |
in | |||||
|
|
|
| ||
56. | Check for a sag in vent pipe. If problem persists, replace inducer motor. | Ð | Ð | 8 | |
|
|
|
|
|
22