Carrier 58MVP Fault Code, ·Thermostat call with SW-1ON, ·Thermostat call with SW-6ON

Models: 58MVP

1 48
Download 48 pages 27.19 Kb
Page 18
Image 18

Fault Code 22

SETUP ERRORÐThis fault indicates that setup switches SW-1 or SW-6 are ON when they should be OFF. The following combinations will cause the fault:

·Thermostat call with SW-1 ON.

·Thermostat call with SW-6 ON.

·SW-1 and SW-6 both ON together.

STEP

ACTION

YES

NO

GO TO

1.

Turn power off and remove blower access panel.

Ð

Ð

2

2.

Make sure thermostat is NOT calling for heating or cooling. Disconnect all thermostat terminal leads

Ð

Ð

3

to make sure.

 

 

 

 

3.

Is setup switch SW-1 in ON position?

4

6

Ð

4.

Put setup switch SW-1 in OFF position.

Ð

Ð

5

5.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

Ð

Ð

INDEX

6.

Is setup switch SW-6 in ON position?

7

8

Ð

7.

Put setup switch SW-6 in OFF position.

Ð

Ð

5

8.

Replace furnace control board.

Ð

Ð

5

Fault Code 23

INVALID BLOWER AIRFLOW SELECTIONÐThis fault indicates improper A/C or CF switch setting. The -14 units can deliver sufficient airflow for 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The -20 unit can deliver sufficient airflow for 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If fault code is flashing, unit still operates, but it defaults to closest allowable airflow.

NOTE: Boards with date codes of 9506 or later will flash fault code and set continuous fan airflow to same airflow as A/C if continuous fan is adjusted to a higher airflow than A/C setting.

STEP

ACTION

YES

NO

GO TO

1.

Turn power off and remove blower access panel.

Ð

Ð

2

2.

Are air conditioning select switches A/C set properly? (See Table 2.)

5

3

Ð

3.

Set air conditioning select switches A/C for proper tonnage as required by condensing unit.

Ð

Ð

4

4.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

Ð

Ð

INDEX

5.

Are continuous fan select switches CF set properly? (See Table 3.)

7

6

Ð

6.

Set continuous fan select switches CF for desired airflow. This setting should normally be set to DE-

 

 

 

FAULT position unless a 2-speed AC/HP is part of system. Use Table 4 for reference on 2-speed

Ð

Ð

4

 

AC/HP airflow requirements.

 

 

 

7.

Are continuous fan select switches CF set to a higher airflow than air conditioning select switches

6

8

Ð

A/C? (See Tables 2 and 3.)

 

 

 

 

8.

Is furnace a 100 size?

11

9

Ð

9.

The problem is in the A/C or CF selection circuit. The maximum cooling or continuous fan airflow for

Ð

Ð

10

this unit will be delivered.

 

 

 

 

10.

Jiggle A/C and CF switches back and forth. If fault code continues to flash, replace furnace control

Ð

Ð

4

board.

 

 

 

 

11.

The problem is in the A/C or CF selection circuit. The minimum cooling or continuous fan airflow for

Ð

Ð

12

this unit will be delivered.

 

 

 

 

12.

Jiggle A/C and CF switches back and forth. If fault code continues to flash, replace furnace control

Ð

Ð

4

board.

 

 

 

 

18

Page 18
Image 18
Carrier 58MVP Fault Code, ·Thermostat call with SW-1ON, ·Thermostat call with SW-6ON, ·SW-1and SW-6both ON together