Carrier 58MVP instruction manual Does fault occur again?

Models: 58MVP

1 48
Download 48 pages 27.19 Kb
Page 31
Image 31

4.

Observe operation of furnace for several minutes or until fault occurs.

Ð

Ð

5

5.

Does fault occur again?

9

6

Ð

6.

Does a different fault occur?

7

8

Ð

7.

Go to page number indicated in Index for fault code flashed.

Ð

Ð

INDEX

8.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

Ð

Ð

INDEX

9.

Is collector box and inducer housing properly draining condensate?

11

25

Ð

10.

Fix problem.

Ð

Ð

8

11.

Are pressure switches wired correctly?

13

10

Ð

12.

Replace pressure switch assembly.

Ð

Ð

8

13.

Do you have 24v between C (Common) on low-pressure switch LPS and Com on furnace control

15

14

Ð

board?

 

 

 

 

14.

The YELLOW wire to low-pressure switch LPS is not making good connection. Repair wire or re-

Ð

Ð

8

place harness.

 

 

 

 

15.

Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. Turn

 

 

 

power on and wait a few sec for self test, then reconnect jumper across R, W/W1, and W2 thermo-

Ð

Ð

16

 

stat terminals.

 

 

 

16.

Do you have 24v between connector terminal PL2-2 and Com on furnace control board when fault

21

18

Ð

occurs?

 

 

 

 

17.

Replace furnace control board.

Ð

Ð

8

18.

Turn power off.

Ð

Ð

19

19.

Do you have continuity across terminal PL2-2 and N.O. (Normally Open) contact on low-pressure

12

20

Ð

switch LPS?

 

 

 

 

20.

The ORANGE wire from low-pressure switch LPS to furnace control board is not making good con-

 

 

 

nection or low gas pressure switch LGPS (when used) is open. Check propane line pressure if us-

Ð

Ð

10

 

ing LGPS otherwise repair wire or replace harness.

 

 

 

21.

Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. Discon-

 

 

 

nect BROWN wire from N.O. (Normally Open) contact on high-pressure switch HPS. Turn power on

Ð

Ð

22

 

and wait a few sec for self test, then reconnect jumper across R and W/W1 thermostat terminals.

 

 

 

22.

Does a Fault Code 32 occur?

17

23

Ð

23.

Reconnect BROWN wire to N.O. (Normally Open) contact on high-pressure switch HPS.

Ð

Ð

24

24.

The problem may be caused by a sag in vent pipe. If this is not the problem and fault still occurs,

Ð

Ð

8

replace pressure switch assembly.

 

 

 

 

25.

The vent tube to drain trap, drain trap, or drain line is clogged.

Ð

Ð

10

31

Page 31
Image 31
Carrier 58MVP instruction manual Does fault occur again?