23. | Are ORANGE and VIOLET wires from PL3 and PL13 making good contact? | 24 | 17 | Ð | |
→24. | Replace entire blower motor or blower control module attached to the blower motor. If you replace | Ð | Ð | 17 | |
the blower control module go to step 26. | |||||
|
|
|
| ||
| Go to page number indicated in Index for CLEANUP AND STARTUP INSTRUCTIONS. If problem |
|
|
| |
→25. | persists on an intermittent basis, replace entire blower motor or blower control module attached to | Ð | Ð | INDEX | |
the blower motor. If your replace the blower control module go to step 26. If problem still persists on | |||||
|
|
|
| ||
| an intermittent basis after replacing blower motor, contact your distributor. |
|
|
| |
|
|
|
|
|
Wait at least 5 minutes after disconnecting line voltage from equipment before opening blower motor to prevent electric shock which can cause personal injury or death.
→26. | Remove tape from door switch and turn power off at main disconnect. | Ð | Ð | 27 | |
→27. | Disconnect PL10 from blower assembly. | Ð | Ð | 28 | |
→28. | Remove control box assembly from blower shelf and position out of the way. | Ð | Ð | 29 | |
→29. | Remove blower assembly from furnace. | Ð | Ð | 30 | |
→30. | Disconnect both | Ð | Ð | 31 | |
sure to depress release latches on connectors or they may get damaged. | |||||
|
|
|
| ||
→31. | Remove two | Ð | Ð | 32 | |
REMOVE TORX HEAD SCREWS located next to | |||||
|
|
|
| ||
→32. | Carefully lift blower control module off blower motor. Depress latch on internal connector to discon- |
|
|
| |
nect blower control module from motor portion of blower motor. DO NOT PULL ON WIRES. GRIP | Ð | Ð | 33 | ||
| PLUG ONLY. |
|
|
| |
| When blower control module is completely detached from blower motor, verify with standard ohm- |
|
|
| |
| meter that the resistance from each motor lead in motor plug to unpainted motor end plate is |
|
|
| |
→33. | greater than 100k ohms. Then verify motor windings are not shorted or open by measuring resis- | Ð | Ð | 34 | |
tance between each combination of pins in motor plug (there are three different combinations, pin | |||||
|
|
|
| ||
|
|
|
| ||
| pins. |
|
|
| |
→34. | Did the motor pass the resistance check? | 35 | 37 | Ð | |
→35. | Does blower wheel turn freely with blower control module removed? | 36 | 37 | Ð | |
→36. | Replace blower control module. Inspect failed blower control module for water damage. If present, | Ð | Ð | 10 | |
find source of water and fix. Check | |||||
|
|
|
| ||
→37. | Replace entire blower motor including blower control module. Inspect blower control module for wa- | Ð | Ð | 10 | |
ter damage. If present, find source of water and fix. Check | |||||
|
|
|
| ||
|
|
|
|
|
28