Carrier 62MB, 62ME, 62MC, 62MD specifications Make Electrical Connections

Models: 62MB 62MD 62MC 62ME

1 82
Download 82 pages 10.42 Kb
Page 47
Image 47
Step 5 — Make Electrical Connections

Step 4 — Installing ERV Transitions — When cou- pling ERV units with Carrier rooftop units an ERV transition is required to link the ERV unit and the Carrier rooftop unit together.

ERV UNIT COUPLED WITH A 3 to 121/2 TON HVAC UNIT — Complete the following steps to install a transition to a 3 to 121/2 ton rooftop unit.

1.Remove the HVAC unit filter door and set aside for later use.

2.Remove the panel shipped on the HVAC unit covering the return air chamber. This panel can be discarded.

3.The 62M ERV transition for 3 to 121/2 ton rooftop units includes a replacement panel to cover the return opening. Install the replacement panel, with hood scoop attached, onto the HVAC unit, over the return air chamber. Screw in place. The return/exhaust scoop will cover part of the return air opening in the HVAC unit.

NOTE: The standard transition does not seal tight around the return air opening on the HVAC unit. This allows for some air to flow back to the HVAC unit and some to be drawn back through the ERV unit.

4.Slide the transition between the ERV unit and the HVAC unit. Refer to Fig. 17-44 to orient the transition. Line up the transition so that it covers the openings in the HVAC unit and the ERV unit. The divider in the transition must separate the supply and return openings in the ERV unit. Screw the mating flanges of the transition to the ERV unit through pre-punched holes. Caulk the seams watertight. Screw the mating flanges on the other side of the transi- tion to the new return air cover panel on the HVAC unit. Caulk seams watertight.

5.On most models the filter access door shipped with the HVAC unit will be reinstalled above the transition.

6.The transition includes a balancing damper to allow for the desired separation of the return/exhaust air between the ERV and HVAC units. This damper has a manual adjustment. During balancing, this damper will be adjusted to achieve desired exhaust cfm. The balancing damper can be accessed through a separate door in the transition or through the HVAC unit’s filter access door. See Fig. 17-44.

Step 5 — Make Electrical Connections

Prior to performing service or maintenance operations on the ERV unit, turn off and disconnect all power switches to the unit. Be aware that there may be more than one discon- nect switch. Electrical shock could cause serious personal injury or death.

IMPORTANT: Only trained, qualified installers and service technicians should install, wire, start-up and service equipment.

POWER SUPPLY — The electrical characteristics of the available power supply must agree with the unit nameplate rating. Supply voltage must be within the limits shown. See Tables 2 and 3 for electrical and configuration data.

ELECTRICAL CONNECTIONS — The ERV unit must have its own electrical disconnect box. If the disconnect option has not been ordered from the factory, it must be field supplied and installed per local codes. See Tables 2 and 3.

If the ERV unit has an electric pre-heater factory installed, it will be wired through the ERV unit disconnect.

NOTE: Most ERV units have electrical interlock safety switches on the access doors, which will not allow the ERV unit to operate if either of the access doors are opened.

Low Voltage Wiring — Wire low voltage per diagrams. For coupled applications, there will be a brown and black wire in the exhaust chamber, which must be tied into the HVAC unit’s indoor fan so that when the indoor fan is activated, the ERV unit will be activated.

48/50TJ, HJ 3 to 121/2 Ton Rooftop Units with Economizers

The brown and black wires can be plugged into the econo- mizer jumper plug on the HVAC unit’s economizer harness. Insert the brown wire from the ERV unit into terminal 4 in the jumper plug and insert the black wire from the ERV unit into terminal 3 in the jumper plug. See Fig. 47.

If the 3 to 121/2 ton rooftop unit has an economizer in- stalled, the economizer will have an end switch attached to the economizer actuator. The end switch must be wired into the ERV unit as shown in Fig. 48.

For ERV units coupled with units with factory-installed economizers, (48/50TM, HJ 15 to 25 ton units 48/50HG, PG 15 to 25 ton units) the ERV transitions to these rooftop units in- clude an economizer end switch. This switch mounts to the hub of the economizer damper gear as shown in Fig. 49. Set the end switch so that the ERV unit’s outside air blower is deactivated during economizer mode.

For stand-alone units, the ERV unit is jumpered from termi- nals 6 and 8 and 7 and 9, providing for continuous operation. The ERV unit should be connected to an on-off device such as a CO2 sensor.

High Voltage Wiring (Fig. 50-53) — Connect high voltage wiring to the disconnect per Fig. 50, 52 and 53. Check blower rotation direction and adjust if necessary.

47

Page 47
Image 47
Carrier 62MB, 62ME, 62MC, 62MD Make Electrical Connections, 48/50TJ, HJ 3 to 121/2 Ton Rooftop Units with Economizers