Carrier 62MD, 62ME, 62MC, 62MB Operating Sequence, Blower Motor Pulley Adjustment - Belt Alignment

Models: 62MB 62MD 62MC 62ME

1 82
Download 82 pages 10.42 Kb
Page 74
Image 74
Fig. 81 — Blower Motor Pulley Adjustment

Fig. 81 — Blower Motor Pulley Adjustment

Fig. 82 — Belt Alignment

Variable Air Volume Option — This option can be used in conjunction with the CO2 sensor option (ordered separately). Outside air and exhaust air blower speeds are independently controlled by variable frequency drives and modulated based upon space occupancy, which can be measured by CO2. The more people in the space the greater the CO2 levels, the more outside air is introduced. This option eliminates over ventilating the space in less than full condi- tions. The ERV unit has completely different electrical charac- teristics when used with a variable air volume option. Refer to Tables 2 and 3.

Operating Sequence

OCCUPIED MODE — While in occupied mode, the 62M ERV will operate per the ERV Timer option (scheduling program), the CO2 sensor input, a combination of the schedul- ing option and CO2 input, or the economizer accessory. Additionally, the low temperature lockout (LTLO) function locks out the 62M ERV if the outdoor-air temperature entering the wheel is below the set point. The LTLO is factory set at –10 F, and can be field adjusted from –30 F to 100 F.

Occupied Mode, with CO2 Sensor — When the CO2 sensor is used, it will measure the space CO2 levels in parts per million (ppm). The 62M ERV CO2 setting is factory set at 1,000 ppm but can be adjusted from 0 ppm to 2,000 ppm. When either the scheduling program and/or the CO2 sensor calls for ERV operation, the ERV will activate the following:

ERV wheel

Outdoor air blower motor

EXH blower motor

Two-position damper opens

NOTE: The two-position damper option may slightly delay activation of the ERV blower motor.

Occupied Mode, with Frost Protection — In the occupied mode, the frost protection option will eliminate frost build-up on the ERV wheel using exhaust air. It is activated via a pressure differential across the ERV wheel. This set point is field set from 0.2 in. wg to 2.0 in. wg and must be set to 150% of the normal static pressure across the wheel. The frost protec- tion feature is automatically locked out above 35 F.

NOTE: If the outdoor-air temperature is below 35 F, a dirty wheel may incorrectly activate the frost control feature if the differential pressure across the wheel exceeds the set point.

When the frost protection option is activated the following will occur:

ERV wheel turns on.

Outdoor air blower motor turns off.

EXH blower motor is on.

Occupied Mode, with the Pre-Heat Option — In the occu- pied mode, the pre-heat option provides frost protection for the ERV wheel and slightly warms the outdoor air. This feature is factory set to activate at –5 F, and can be field adjusted from –30 F to 100 F. It is recommended that this set point be set at the frost threshold for the region in which it is used.

If desired, this feature may also be activated via a field supplied pressure differential switch to determine if frost build up has occurred on the ERV wheel.

Occupied Mode, with the Economizer Accessory — When using the economizer option, this allows for up to 100% outside air to be brought in for free cooling. During free cooling, the rooftop unit mechanical cooling may or may not be operating depending on the set points used with the rooftop unit. When using the economizer accessory, it is recommended that the minimum position be set to the closed position and the ERV should be set such that it is locked out when the econo- mizer opens far enough to bring in the same level of outdoor air as the ERV.

If desired, this feature may also be activated via a field-supplied pressure differential switch to determine if frost build- up has occurred on the ERV wheel.

During free cooling, the following occurs:

ERV wheel is turned off.

Outdoor air blower is turned off.

EXH blower motor turns on.

Two-position outdoor-air damper is closed (if used).

Two-position EXH damper is opened (if used).

Stop/jog option will periodically rotate the ERV wheel to clean it during wheel bypass operation. This feature is factory set to activate every 10 minutes, for 20 seconds of operation. Both settings can be adjusted from 0 to 10 minutes.

Wheel Bypass Option — When using the wheel bypass option (with the stop/jog option), this allows free cooling through the wheel limited by the ERV airflow cfm limits. With this option the unit can be in free cooling or not depending on the tempera- ture of the outdoor-air compared to the set point. When not in free cooling, the ERV will not operate. When in free cooling:

ERV wheel is turned off.

Outdoor-air blower is turned on.

74

Page 74
Image 74
Carrier 62MD, 62ME, 62MC, 62MB specifications Operating Sequence, Blower Motor Pulley Adjustment - Belt Alignment