Installing the Fan Tray Power Cable for AC-Input Systems

Connecting Power to the Fan Tray

Installing the Fan Tray Power Cable for AC-Input Systems

Note The fan tray ships with power wires secured at each terminal block. Use these wires to connect the fan tray to the 3000 W AC-input power supply using the supplied cables. If you have redundant power supplies, repeat the steps in this section for the redundant power supply.

To connect the high speed fan tray to the 3000 W AC-input power supply, follow these steps:

Step 1 Connect the female end of the supplied power cable (see Figure 9) to the fan tray wire connector. Press the two ends together until you hear a click.

Figure 9 Cable Connectors

To fan cable

To power supply

105076

Step 2 On the power supply, loosen the thumb screw on the external power connector cover and lift up the cover. (See Figure 10.)

Figure 10 External Power Connector Cover

OUTPUT 42V /17A

OUTPUT 42V /17A

1

2

42V

/17A

OK

42V

/17A

OK

+

105083

Step 3 Connect the male end of the supplied power cable to the female end of the external power connector on the power supply until you hear a click.

Step 4 If you have redundant power supplies, repeat the steps in this section for the redundant power supply.

Catalyst 6509-NEB Switch and Cisco OSR-7609 Router Upgrade Note