Chapter 2 Installing a Cisco Nexus 7010 Chassis

Grounding the Cisco Nexus 7010 Chassis

Se n d d o c u m e n t c o m m e n t s t o n ex u s 7 k - d o c f e e d b a ck @ c i s c o . c o m

1

NRTL listed 45-degree grounding lug

2

Grounding cable with 0.75 in. of insulation stripped from the end

Step 3 Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely attached to the ground lug by attempting to pull the wire out of the crimped lug.

Step 4 Remove the adhesive label from one of the two system grounding pads, and secure the grounding wire lug to the grounding pad with two M4 screws. Figure 2-6shows the location of the grounding pads on the front side of the chassis. Figure 2-7shows the location on the rear of the chassis. Ensure that the grounding lug and the grounding wire do not interfere with other device hardware or rack equipment.

Figure 2-6 Grounding Port on the Front of the Cisco Nexus 7010 Chassis

187225

Grounding port

 

 

Cisco Nexus 7000 Series Hardware Installation and Reference Guide

 

 

 

 

 

 

OL-18634-01

 

 

2-13

 

 

 

 

 

Page 45
Image 45
Cisco Systems 7000, UCSCPCIECSC02, N7KC7004, N7KC7018RF manual Grounding Port on the Front of the Cisco Nexus 7010 Chassis