Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-18634-01
Chapter 3 Installing a Cisco Nexus 7018 Chassis
Installing the Front Door and Air Intake Frame
To install the front door and air intake frame to the Cisco Nexus 7018 cable management system , follow
these steps:
Step 1 Position the left door stopper (700-27454-01) on the middle of the left cable management assem bly and
fasten it with two M3x10 pan-head screws as shown in Figure 3-13. Tighten these two screws to 5 to 7
in. lbs.
Figure 3-13 Attaching the Left Door Stopper
Step 2 Position the right door stopper (700-27592-01) on the middle of the right cable management assem bly
and fasten it with two M3x10 pan-head screws as shown in Figure 3-14. Tighten these two screws to 5
to 7 in. lbs.
192196
3
1
2
1Left door stopper identified with an L on the
bottom of the base.
2Two M3x10 screws that fasten the stopper to
the cable management assembly.
3Screw holes on the cable management
assembly.