Step 4 Connect the other end of the power cables to an AC power source.

Chapter 2 Installing the Cisco MDS 9200 Series

Starting Up the Switch

Se n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a ck - d o c @ c i s c o . c o m

Step 2 Verify that both power supplies and the fan module are installed.

Step 3 Verify that the power switches on both power supplies are off, and then plug the power cables into the power supplies and tighten the screws on the power cable retainers to ensure the cables cannot be pulled out.

Note Depending on the outlet receptacle on your power distribution unit, you may need the optional jumper power cord to connect the Cisco MDS 9200 Series to your outlet receptacle. See the “Jumper Power Cord” section on page C-11.

Step 4 Connect the other end of the power cables to an AC power source.

Step 5 Ensure that the switch is adequately grounded as described in the “Installing the Switch in a Cabinet with Insufficient Front Clearance” section on page 2-11, and that the power cables are connected to outlets that have the required AC power voltages (see the “Weight of Modules” section on page B-3).

Step 6 Flip the power switches on the power supplies to the on () position. The switch boots automatically. Step 7 Listen for the fans; they should begin operating when the switch is powered on.

Caution Do not operate the switch without a functioning fan module except for during the brief fan module replacement procedure. Cisco MDS 9000 Family switches can operate for only a few minutes without any functioning fan modules before they begin to overheat.

Step 8 After the switch boots, verify that the LED behavior is as follows:

Fan module: Status LED is green.

Power supplies:

Input Ok LED is green.

Fan Ok LED is green.

Output Fail LED is off.

Supervisor, switching, or services modules:

During initialization, the status LED on the module flashes orange once, remains orange during diagnostic boot tests, then turns green when the module is operational (online). If the system software is unable to start up, this LED remains orange or turns red.

After initialization, the status LED is green, indicating that all chassis environmental monitors are reporting that the system is operational. If this LED is orange or red, then one or more environmental monitor is reporting a problem.

The Link LEDs for the Ethernet port should not be on unless the cable is connected.

Note The link LEDs for the Fibre Channel ports remain yellow until the ports are enabled, and the LED for the MGMT 10/100 Ethernet port remains off until the port is connected.

Step 9 Try removing and reinstalling a component that is not operating correctly. If it still does not operate correctly, contact your customer service representative for a replacement.

 

 