C o n t r o l S e t u p

1/32 DIN Watlow SD controller Setup Sheet

Enter the following parameters

Menu

Parameter

Description

Setting

Set Up Page

Sen

Input sensor type

RTD

up & down for

C-F

Temperature Units (degrees)

F

3 seconds

S.dec

Temperature Decimal Places

0

 

IS.en

Infosense

no

 

SP.Lo

Set Point Low Limit

40.0

 

SP.hi

Set Poing High Limit

65

 

Ftr.e

Input Filter

Both

 

Flt.r

Filter value - Seconds

5

 

Ot1

Output 1 function

heat

 

Ctr1

Control Method 1

ftb

 

Ftb1

Cycle time 1

10

 

PL 1

Power Limit 1

100%

 

PSL1

Output Power Limit Sacle Low 1

0%

 

PSH1

Output Power Limit Sacle High 1

90%

 

nLF1

Output Non-Linear Function 1

Off

 

Ot2

Output 2 Function - SP devaition

dE.AL

 

hys2

Alarm Hysteresis 2

1.5F

 

Lgc2

Alarm relay state on alarm - open

Al o

 

Lat2

Alarm 2 latching

nLat

 

dSP2

Alarm 2 Message

on

 

ACLF

AC line frequency

60

 

Unit

Units of Measurement

SI

 

I.Err

Input error latching

nLat

 

FAIL

Input Error Failure Mode

bPLS

 

Man

Manual Error Level

0%

 

dSP

Active Displays

nor

 

rP

Ramping Mode

off

 

LOC

Security Lockout

3

 

 

 

 

Programming

Adv and INF keys 6 seconds

 

 

 

P1

Temperature Units - C-F

F

 

P2

Low Temp Dev. alarm - A2.Lo

-4

 

P3

High Temp dev Alarm - A2.HI

20

 

P4

Proportional Band Hot Gas - pb.ht

3

 

P5

Intergral Hot Gas - It.ht

3.4

 

P6

Derivative - dE.ht

0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A p p e n d i x l I - 1