C o n t r o l S e t u p
1/32 DIN Watlow SD controller Setup Sheet
Enter the following parameters
Menu | Parameter | Description | Setting |
Set Up Page | Sen | Input sensor type | RTD |
up & down for | Temperature Units (degrees) | F | |
3 seconds | S.dec | Temperature Decimal Places | 0 |
| IS.en | Infosense | no |
| SP.Lo | Set Point Low Limit | 40.0 |
| SP.hi | Set Poing High Limit | 65 |
| Ftr.e | Input Filter | Both |
| Flt.r | Filter value - Seconds | 5 |
| Ot1 | Output 1 function | heat |
| Ctr1 | Control Method 1 | ftb |
| Ftb1 | Cycle time 1 | 10 |
| PL 1 | Power Limit 1 | 100% |
| PSL1 | Output Power Limit Sacle Low 1 | 0% |
| PSH1 | Output Power Limit Sacle High 1 | 90% |
| nLF1 | Output | Off |
| Ot2 | Output 2 Function - SP devaition | dE.AL |
| hys2 | Alarm Hysteresis 2 | 1.5F |
| Lgc2 | Alarm relay state on alarm - open | Al o |
| Lat2 | Alarm 2 latching | nLat |
| dSP2 | Alarm 2 Message | on |
| ACLF | AC line frequency | 60 |
| Unit | Units of Measurement | SI |
| I.Err | Input error latching | nLat |
| FAIL | Input Error Failure Mode | bPLS |
| Man | Manual Error Level | 0% |
| dSP | Active Displays | nor |
| rP | Ramping Mode | off |
| LOC | Security Lockout | 3 |
|
|
|
|
Programming | Adv and INF keys 6 seconds |
|
|
| P1 | Temperature Units - | F |
| P2 | Low Temp Dev. alarm - A2.Lo | |
| P3 | High Temp dev Alarm - A2.HI | 20 |
| P4 | Proportional Band Hot Gas - pb.ht | 3 |
| P5 | Intergral Hot Gas - It.ht | 3.4 |
| P6 | Derivative - dE.ht | 0.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A p p e n d i x l I - 1