FIREPLACE INSERT INSTALLATION

Installing Pellet Inserts into Factory Built or Masonry Fireplaces . . . cont

Means must be provided for removal of the insert to clean the chimney liner.

Inserts that project in front of the fireplace must be supplied with appropriate supporting means.

A permanent metal warning label must be attached to the back of the fireplace stating that the fireplace must be restored to its original condition for safe use without the insert.

This sticker is supplied in the “Owners Manual” and accessories packaging, found in the unit. (See the following statement)

THIS FIREPLACE HAS BEEN ALTERED TO ACCOMMODATE A FIREPLACE INSERT AND SHOULD BE INSPECTED BY A QUALIFIED PERSON PRIOR TO RE-USE AS A CONVENTIONAL FIREPLACE!

When installing into a masonry chimney, it is recommended that the exhaust vent be extended to the top of the chimney as shown in figure 26.

However, if the vent pipe does not extend to the top of the chimney, the pipe must extend a minimum of 18” above the damper.

You must seal the damper area with a steel plate when using the direct connection method.

FULL CHIMNEY RELINE

DIRECT CONNECTION

Note: This installation is recommended

Note: This installation not allowed in Canada

for all chimney installations!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8”

8”

 

6”

6”

 

Glow Boy Pellet & Biomass

www.glowboystoves.com

21

 

 

 

Page 21
Image 21
Dansons Group FGB, IGB manual Full Chimney Reline Direct Connection