Dayton Operating Instructions and Parts Manual

Models 2ZRP8, 2ZRP9

11.If GFCI receptacle(s) test correctly, firmly push the reset button to restore power. A distinctive click should be heard or felt when this is complete. IF THE RECEPTACLE(S) DO NOT RESET PROPERLY, DO NOT USE THE RECEPTACLE(S). SEE DEALER FOR SERVICE IMMEDIATELY.

12.Turn idle control switch to ON position. Loads can now be applied to unit.

NOTE: This engine is equipped with a “Low Oil” shutdown system for engine protection. The engine stops when the oil level gets too low. The engine will not restart without adding oil. Refer to Preparing the Generator; Engine Fuel Capacity for instructions on adding oil.

NOTE: While the engine is idling, the generator voltage is automatically reduced to reduce generator temperatures. The voltage will return to normal levels immediately upon the application of load.

Electric Start

NOTE: Read Operator’s Manual carefully before operating this unit. Always make sure the unit is level and properly grounded. Check engine oil before starting.

1.Open fuel valve on unit or engine.

2.Turn the idle control switch to the OFF position.

3.Move choke lever to full choke. If re- starting a warm engine, the choke should be left in the off position.

4.Turn the engine ignition switch to the ON position.

5.Start the engine by turning the key switch fully clockwise until the engine starts, then release the switch.

NOTE: Do not crank the engine continuously for more than 30 seconds at a time. If the engine does not start, allow for a 3 minute cool down period

between starting attempts. Failure to follow these guidelines can damage the starter motor.

If the starter does not turn the engine over, shut offthe starter immediately. Do not make further attempts to start the engine until the condition is corrected. Do not jump start using another battery.

6.Once engine has started, slowly move choke lever to no choke.

7.Allow the unit to run for two (2) minute warm-up.

8.Turn main breaker to ON position (GEN-6000 units only).

9.Test the GFCI receptacle(s) on the unit. Push the test button. The reset button should pop out and there should be no power at the receptacle. Apply a test load or lamp to each receptacle to verify. IF THE RESET BUTTON DOES NOT POP OUT, DO NOT USE THE RECEPTACLES(S). SEE DEALER FOR SERVICE IMMEDIATELY.

10.If GFCI receptacle(s) test correctly, firmly push the reset button to restore power. A distinctive click should be heard or felt when this is complete. IF THE RECEPTACLE(S) DO NOT RESET PROPERLY, DO NOT USE THE RECEPTACLE(S). SEE DEALER FOR SERVICE IMMEDIATELY.

11.Turn idle control switch to ON position. Loads can now be applied to unit.

NOTE: This engine is equipped with a “Low Oil” shutdown system for engine protection. The engine stops when the oil level gets too low. The engine will not restart without adding oil. Refer to Preparing the Generator; Engine Fuel Capacity for instructions on adding oil.

SHUTDOWN

1.Remove all load by turning off electrical appliances and unplugging electric cords.

2.Allow engine to run at idle speed to cool for two (2) minutes.

NOTE: Failure to allow the engine to cool at idle for two (2) minutes may result in damage to the generator.

3.Turn engine key or ignition switch off. 4.Close fuel valve on unit or engine.

Maintenance

GENERATOR MAINTENANCE

Keep all air vents clear.

Keep the generator clean. DO NOT spray with water.

Periodically check all fasteners and tighten, see the periodic maintenance chart.

GFCI TEST RECORDS: As with any other safety devices, the GFCIs supplied with these generators must be checked every month to insure that they are functioning properly. To test the GFCIs, follow the instructions and then enter the date of the test below.

1.With the generator running and the idle control switch in the “START” position, push the “TEST” button. The “RESET” button should pop out. This should result in the power being off at both outlets of the duplex receptacle. Verify this by plugging a test lamp into each outlet.

IF THE RESET BUTTON DOES NOT POP

OUT, DO NOT USE THE RECEPTACLE(S). SEE AUTHORIZED Dayton Customer Service Representative FOR SERVICE IMMEDIATELY.

2.If the GFCI test correctly, restore power by FIRMLY pushing the “RESET” button back in until you

E

N G L I S H



Page 7
Image 7
Dayton 2ZRP8, 2ZRP9 specifications Electric Start, Shutdown, Generator Maintenance