Dell J715N, K789N, K788N, K806N, 500W, H914N, H900N, H965N Configuring Automatic on Battery Shutdown

Models: J716N 500W H965N H900N J715N K788N K806N H914N K789N

1 63
Download 63 pages 52.12 Kb
Page 43
Image 43
Configuring Automatic on Battery Shutdown

Configuring Automatic on Battery Shutdown

If set to Off (default), the load segment turns off only when commanded manually by the Manual background button, an external command, or through the display (Control > Load Segments).

If set to zero seconds (0s), the load segment turns off automatically when the UPS on Battery state activates.

If you select a value, the load segment turns off automatically after the selected delay while the UPS operates on battery, but the shutdown is cancelled if the utility returns before the delay has expired.

To set the shutdown times for each load segment:

1Press the Manual background button for one second to go to the main menu selection and scroll down to the Settings menu using the Manual background button.

2Press the Manual background button to enter the Settings menu.

3Use the Manual background button to scroll to the Automatic on Battery Shutdown option and press the Manual background button. The options display and the current settings flash when selected.

4Set the shutdown delay for one load segment using the Manual background and Manual background buttons.

5Press the Manual background button to confirm.

6Set the shutdown delay for the other load segment if applicable.

7Press the Manual background button to confirm.