Dell H914N, K789N Configuration, Voltage, Fuses, Type, Charging, Monitoring, Battery Runtimes

Models: J716N 500W H965N H900N J715N K788N K806N H914N K789N

1 63
Download 63 pages 52.12 Kb
Page 58
Image 58
Table 15. Battery

Table 15. Battery

Configuration

500W: (2) 12V, 7 Ah internal batteries (no EBM)

 

1000W: (3) 12V, 9 Ah internal batteries; (6) 12V, 9 Ah EBM

 

1920/1500W: (6) 12V, 9 Ah internal batteries; (12) 12V, 9 Ah EBM

 

 

Voltage

500W: 24 Vdc internal

 

1000W: 36 Vdc internal, 36 Vdc EBM

 

1920/1500W: 72 Vdc internal, 72 Vdc EBM

 

 

 

Fuses

500W internal battery: (2) 40A fuses

1000W, 1920W EBMs: (4) 30A fuses

 

1000W, 1920/1500W internal batteries:

 

 

(2) 30A fuses

 

 

 

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

 

 

Charging

Internal batteries: approximately 4 hours to 90% (8 hours for 500W models) usable

 

capacity at nominal line and no supplementary power supply load

 

EBMs: approximately 12 hours to 90% from a discharge of 50% rated load

 

 

Monitoring

Advanced monitoring for earlier failure detection and warning

 

 

Battery Runtimes

Internal batteries: 5 minutes at full load/14 minutes at half load

 

UPS with one EBM attached: 19 minutes at full load/45 minutes at half load

*Battery runtimes are approximate and vary depending on the load configuration and battery charge.

Input Filter

AVR

Output

Filter

Charger

Battery

DC/DC

Converter

DC/AC Inverter

Figure 27. Line-Interactive UPS Block Diagram

58 Specifications

Page 58
Image 58
Dell H914N, K789N, K788N, K806N, 500W, H900N Configuration, Voltage, Fuses, Type, Charging, Monitoring, Battery Runtimes