38 Operation

Table 7. Settings (continued)

Description

Available Settings

Default Setting

 

 

 

Battery Saving Mode

[Disabled] [10%] [20%] [30%]...[100%]

Disabled

 

The UPS output is turned off in five minutes if the

 

 

UPS is on battery and output power is below the

 

 

selected level.

 

 

 

 

On Battery Notice Delay

[0] [1s] [2s]...[99s]

0s

 

The UPS issues a “UPS on battery” notice in the

 

 

specified number of seconds after the UPS starts to

 

 

discharge the batteries.

 

 

 

 

Site Wiring Fault Alarm

[Enabled] [Disabled]

Disabled for 208V

 

 

models; Enabled for

 

 

all others

 

 

 

External Battery Module (EBM)

[0] [1]

0

 

See “Configuring the UPS for an EBM” on page 44.

 

 

 

 

Charger

[Enabled] [Disabled]

Enabled

 

If Enabled, batteries charge normally.

 

 

If Disabled, the battery charger is off.

 

 

 

 

Battery Charge % to Restart

[0%] [10%] [20%] [30%]...[100%]

0%

 

When enabled, automatic restart is made when the

 

 

battery charge state reaches the selected level. If set

 

 

to 0, the feature is disabled.

 

 

 

 

Battery Low Alarm

[Immediate] [2 min] [3 min] [5 min]

3 min

 

If you select a value, the battery low alarm triggers

 

 

when the set amount of backup time

 

 

(approximately) remains in the batteries.

 

 

 

 

Automatic Battery Tests

[Enabled] [Disabled]

Enabled

 

See “Running Automatic Battery Tests” on page 45.

 

 

 

 

38 Operation