Dell J716N, K789N Storing the UPS and Batteries, When to Replace Batteries, Testing Batteries

Models: J716N 500W H965N H900N J715N K788N K806N H914N K789N

1 63
Download 63 pages 52.12 Kb
Page 53
Image 53
Storing the UPS and Batteries

Storing the UPS and Batteries

If you store the UPS for a long period, recharge the battery every 6 months by plugging the UPS into a power outlet. The batteries charge to 90% capacity in approximately 4 hours (8 hours for 500W models). However, it is recommended that the batteries charge for 48 hours after long-term storage.

Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never recharged, do not use the UPS. Contact your service representative.

When to Replace Batteries

When the status summary screen displays the UPS fault icon with the “Service Battery” alarm and the audible alarm sounds continuously, the batteries may need replacing. Contact your service representative to order new batteries.

NOTE: With the user-replaceable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load.

Testing Batteries

For a battery test to run:

SThe batteries must be fully charged.

SThe UPS must be in Normal mode with no active alarms.

SThe load must be higher than 10%.

To test the batteries:

1Plug the UPS into a power outlet for at least 48 hours to charge the batteries.

2Press the When to Replace Batteries button for one second to go to the main menu selection and scroll down to the Control menu using the Testing Batteries button.

3Press the Manual background button to enter the Control menu.

4Use the Manual background button to scroll to the Battery Test option.

5Press the Manual background button to start the battery test.

During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25% of the original expected runtime. The front panel displays “Battery test running” and the percentage of the test completed. The results display on the UPS front panel when complete.

UPS Maintenance