DeviceNet Network Scanner DVPDNET-SL

(3)Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud rate and communication format.

Item

Function

Default

COM Port

COM port on the PC to be used to

COM1

communicate with DVP-SV

 

 

Address

Communication address of DVP-SV

01

 

 

 

Baud rate

Communication speed between the PC and

9,600 (bps)

DVP-SV

 

 

Data Bits

Communication protocol between the PC and

7

 

 

Parity

Even Parity

DVP-SV

 

 

Stop Bit

1

 

 

 

 

Mode

Communication mode between the PC and

ASCII

DVP-SV

 

 

Click on “OK” and return to the main page.

(4) Select “Network” => "Online”, and the “Select Communication Channel” dialog box will appear.