DeviceNet Network Scanner DVPDNET-SL

„ Compulsory settings in IFD9502

 

Parameter

Set value

Explanation

 

Node address

02

Set the node address of IFD9502 to “02".

 

 

 

 

 

Baud rate

500kbps

Set the communication speed of IFD9502 and bus to

 

“500kbps”.

 

 

 

„ Compulsory settings in VFD-B

 

 

 

 

 

 

Parameter

Set value

Explanation

 

02-00

04

The main frequency is operated on RS-485 interface.

 

 

 

 

 

02-01

03

The operation commands are operated on the communication

 

interface. Operation by keys is valid.

 

 

 

 

09-00

01

Communication address of VFD-B: 01

 

 

 

 

 

09-01

03

Baud rate: 38,400

 

 

 

 

 

09-04

03

Modbus RTU mode. Data format <8, N, 2>

 

 

 

 

„Explanations on devices

PLC device

Content

 

 

 

 

 

 

Explanation

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

 

 

 

 

D6250

0101Hex

 

 

ReqID = 01Hex

 

Command = 01Hex

 

 

 

 

 

 

 

 

 

 

D6251

0005Hex

 

 

Port = 00Hex

 

 

Size = 05Hex

 

 

 

 

 

 

 

Request

D6252

0E02Hex

 

Service Code = 0EHex

 

MAC ID = 02Hex

message

D6253

0001Hex

High bye of Class ID =00Hex

Low byte of Class ID = 01Hex

editing area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6254

0001Hex

High byte of Instance ID =

Low byte of Instance ID =

 

 

 

 

 

00Hex

 

 

 

01Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6255

0001Hex

 

 

 

N/A

 

Attribute ID = 01Hex

 

 

 

 

 

 

 

 

 

 

D6000

0101Hex

 

 

ReqID = 01Hex

 

 

Status = 01Hex

Response

D6001

0002Hex

 

 

Port = 00Hex

 

 

Size = 02Hex

message

D6002

8E02Hex

 

Service Code = 8EHex

 

MAC ID = 02Hex

editing area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6003

031FHex

High byte of Service Data =

Low byte of Service Data =

 

 

 

 

 

03Hex

 

 

 

1FHex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) PLC program

M1002

ZRST D6000 D6031

ZRST D6250 D6281

M0

Reset response message editing area & request message editing area

MOV

H0101

D6250

ReqID = 01, Command = 01

MOV

H0005

D6251 Port = 00, Size = 05

MOV

H0E02

D6252

Service Code = 0E, MAC ID = 02

MOV

H0100

D6253

Class ID to be read = 01

MOV

H0100

D6254

Instance ID to be read = 01

MOV

H0100

D6255

Attribute ID to be read = 01

DVP-PLC Application Manual