DeviceNet Network Scanner DVPDNET-SL
DVP-PLC Application Manual 9
Mapped D registers
DVPDNET-SL
index Output mapping Input mapping
1 D6250 ~ D6497 D6000 ~ D6247
2 D6750 ~ D6997 D6500 ~ D6747
3 D7250 ~ D7497 D7000 ~ D7247
4 D7750 ~ D7997 D7500 ~ D7747
5 D8250 ~ D8497 D8000 ~ D8247
6 D8750 ~ D8997 D8500 ~ D8747
7 D9250 ~ D9497 D9000 ~ D9247
8 D9750 ~ D9997 D9500 ~ D9747

4.2 I/O Mapping Table

Output mapping are Input mapping area
D register Mapping area Data length D register Mapping area Data length
D6250 ~ D6281 Explicit message
program request 32 words D6000 ~ D6031 Explicit message
program response 32 words
D6282 ~ D6285 Bit-strobe command 4 words D6032 ~ D6035 Status of nodes in the
scan list 4 words
D6286 Reserved 1word D6036 DVPDNET-SL status 1 word
D6287 ~ D6476 DeviceNet output data 190 words D6037 ~ D6226 DeviceNet input data 190 words
D6477 ~ D6497 Reserved 21 words D6227 ~ D6247 Reserved 21 words
5 Constructing DeviceNet Network
In this section, we will present an application example, illustrating how to construct a DeviceNet network and
the configuration of the network. Before constructing a network, you have to first know clearly what the network
is for and start a preliminary planning for the data to be exchanged. The plan shall include the maximum
communication distance, slaves to be used, total length of data to be exchanged and so on. These information
will decide whether the network you construct is a reasonable one, or if it satisfies your needs, and even affect
the later-on network sustainability and flexibility of network capacity upgrade.

5.1 How to Construct a DeviceNet Network

Target Using a remote digital I/O module to control RUN/STOP of VFD-B AC motor drive.
1. The connection