Quad Amp Hardware Reference Manual
Note:
Jumpers E1A, E1B, E2A, E2B, E3A, E3B, E4A, E4B must be installed on the current sense board so that the
Once such a condition occurs, the PLC notifies the user with an
LED Fault Indicator
The fault information is reported as a
Global faults are numbered in the range
If there is no fault condition, the display will indicate a 0. With a 0 in the display, the left decimal point shall be lit if any of the axes is enabled. The right decimal point shall be lit if the internal shunt is active.
The LED fault indicator will provide a following common fault code for the Quad Amplifier:
0 | Everything O.K. |
1 | General firing module fault |
2 | Module over temperature |
3 | Ground fault |
4 | Over current (surge) fault |
5 | Motor over temperature |
6 | TBD |
7 | TBD |
8 | |
9 | High PWM frequency fault |
A | DAC (nonPWM) fault |
B | Bus over voltage |
C | Bus under voltage |
D | General Power Supply/Soft Start fault |
E | TBD |
F | TBD |
Global Fault Only
In the case of a global fault only, the display will indicate the fault number from
Global and Axis-Specific Faults
In the case of an
Axis-Specific Fault Only
In the case of an
Axis 1: | Left off | Right off |
Axis 2: | Left off | Right on |
Axis 3: | Left on | Right off |
Axis 4: | Left on | Right on |