
VENTING INSTALLATION
VENTING INSTALLATION
9
A 
The following section is provided as a guide to a standard 
Standing codes requirements concerning 
This gas appliance must be vented to the outdoors only and may not be terminated into an attic space or into a chimney flue servicing a 
This appliance may be vented through a manufactured chimney system or a masonry chimney using a 
The examples shown in Figure 10 are typical of most 
Example 1: Shows the minimum allowable system height and lateral offset for a 60° degree or greater inclination. Code specifies that offsets at 60° degrees or greater are considered horizontal and must follow the 75% percent rule for lateral to total vertical system height. Codes also allows only one offset in the total system when at 60° degrees or greater. The total vertical height in this example represents the minimum height of 8 feet and therefore the allowable lateral is 6 feet when the 75% percent rule applies. If the lateral length must exceed 75% then the system must be sized in accor- dance with the Category I venting tables.
Example 2: Shows a multiple offset each at 45° degrees of inclination. Multiple offsets are permitted if they do not exceed 45° degrees of inclination. The total lengths of the two offsets are not required to meet the 75% percent allowable rule.
Example 3: Shows a single offset at 45° degrees of inclination and therefore the lateral length at 10 feet of offset does not have to meet the 75% percent rule.
In each case the offsets must be supported and firestops must be positioned wherever the vent must pass through a 
| 
 | 
 | Listed | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | Vent Cap | 
 | 
 | Listed | Listed | |
| 
 | 
 | 
 | 
 | 
 | Vent Cap | ||
| 
 | 
 | 
 | 
 | 
 | Vent Cap | ||
| 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | Maintain | 
 | Maintain | 
 | 
 | 
 | 
 | 
| 
 | 
 | Listed | 
 | 
 | 
 | Maintain | |
| 
 | Listed | 
 | 
 | 
 | 
 | ||
| 
 | 
 | Clearance | 
 | Maintain | 
 | Listed | |
| 
 | Clearance | 
 | 
 | 
 | |||
| 
 | 
 | Support Each | 
 | Listed | 
 | Clearance | |
| 
 | 
 | 
 | 
 | 
 | |||
| 
 | 
 | 
 | Lateral At | 
 | Clearance | 
 | 
 | 
| 
 | 
 | 
 | Least Every | 45° | 
 | 
 | 
 | 
| 
 | 
 | 60° | Six (6) Feet | 12' Min. | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 8' | 
 | 
 | 
 | 45° | 10' | |
| 
 | 6' | 
 | 
 | 
 | |||
| 12' Min. | Position | 
 | 45° | Position | 
 | 12' Min. | |
| 
 | Position | 
 | |||||
| 
 | Firestop | 
 | Firestop | 
 | Firestop | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | Maintain | 
 | Maintain | 
 | 
 | Maintain | 
| 
 | 
 | Listed | 
 | Listed | 
 | 
 | Listed | 
| 
 | 
 | Clearance | 
 | Clearance | 
 | 
 | Clearance | 
| EXAMPLE 1 | EXAMPLE 2 | EXAMPLE 3 | 
Figure 10 - Typical B-Vent  Configuration



 For more information, visit www.desatech.com
For more information, visit www.desatech.com
