Desa CDV34PA, CDV34NA Installation for Vertical Termination, Flat Ceiling Installation

Models: CDV34PA CDV34NA

1 34
Download 34 pages 36.97 Kb
Page 12
Image 12

CDV34NA, PA

DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)

VENTING INSTALLATION

Continued

INSTALLATION FOR VERTICAL TERMINATION

1.Determine the route your vertical vent- ing will take. If ceiling joists, roof rafters, or other framing will obstruct the venting system, consider an offset (see Figure 21) to avoid cutting load bearing members. Note: Pay special attention to these installation instruc- tions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum verti- cal rise of the venting system and any maximum horizontal offset limitations. Offsets must fall within the parameters shown in Figure 8 on page 6.

2.Set the fireplace in desired location. Drop a plumb line down from the ceil- ing to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating hole in the ceil- ing. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Roof

Flashing

Wall Strap

45° Elbow

Ceiling Firestop

Figure 21 - Offset with Wall Strap and 45°

Flat Ceiling Installation

1.Cut a 10" square hole in the ceiling us- ing the locating hole as a center point. The opening should be framed to 10"x10" (254mm x 254mm) inside di- mensions, as shown in Figure 12 on page 9 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceil- ing or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 22).

2.Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. All connections must be sealed with high temperature silicone sealant as specified in the second warning state- ment on page 7. Be sure all pipe and elbow connections are fully twist- locked (see Figure 11, page 9).

3.Cut a hole in the roof using the locating hole as a center point. (Cover any ex- posed open vent pipes before cutting hole in roof.) The 10"x10" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combus- tible materials. Frame the opening as shown in Figure 12 on page 9.

If area above is a room, install firestop above framed hole.

If area above is not a room, install firestop below framed hole.

4.Connect a section of pipe and extend up through the hole.

Note: If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for

this purpose (see Figure 21). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less re- striction to the flow of the flue gases and intake air.

5.Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure 21. There must be a 1" clearance from the vent pipe to combustible materials.

6.Continue to add pipe sections until the height of the vent cap meets the mini- mum building code requirements de- scribed in Figure 8 on page 6. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs, and other similar fac- tors may cause poor draft or down-draft- ing in high winds. Increasing the vent height may solve this problem.

7.Twist-lock the vent cap onto the last section of vent pipe and seal outer pipe connection with high temperature sili- cone sealant as specified in the second warning statement on page 7.

Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclo- surewithstandardconstructionmaterial.Make sure and meet the minimum allowable clear- ances to combustibles. Do not fill any of the required air spaces with insulation.

Cathedral Ceiling Installation

1.Remove shingles or other roof cover- ing as necessary to cut the rectangular hole for the support box. Mark the out- line of the cathedral ceiling support box on the roof sheathing using the locat- ing hole as a center point.

2.Cut the hole 1/8" larger than the sup- port box outline (see Figure 23, page 13).

Elbows

Figure 22 - Installing Firestop

12

105982

Page 12
Image 12
Desa CDV34PA, CDV34NA Installation for Vertical Termination, Flat Ceiling Installation, Cathedral Ceiling Installation

CDV34PA, CDV34NA specifications

Desa CDV34NA and CDV34PA are two prominent models in the Desa vent-free gas fireplace series, renowned for their efficiency, craftsmanship, and modern design. These fireplaces offer an ambient warmth while combining style with practicality, making them a popular choice for homeowners looking to enhance their living spaces.

One of the key features of the CDV34NA and CDV34PA is the vent-free technology. This innovative design allows for the direct burning of gas without the necessity of a chimney or venting system. As a result, these fireplaces can be installed in various locations within the home, providing flexibility that traditional fireplaces cannot match. The absence of a flue system also means that no heat is lost during the exhaust process, allowing for maximum energy efficiency.

Both models are equipped with advanced safety features. They include an Oxygen Depletion Sensor (ODS) that automatically shuts off the unit if oxygen levels fall below a safe threshold. This technology not only ensures the safety of users but also enhances peace of mind while operating the fireplace. Additionally, the CDV34 series features a built-in thermocouple that regulates the temperature, providing an added layer of safety by preventing overheating.

When it comes to aesthetics, the CDV34NA and CDV34PA do not disappoint. They feature a modern, sleek design that complements a variety of interior decors. Available in stylish finishes, these units can seamlessly blend into contemporary homes or traditional settings. The large viewing windows provide a captivating view of the flames, creating an inviting ambiance ideal for any gathering.

Performance-wise, both models deliver impressive heating capabilities. With adjustable heat output settings, users can customize the warmth to suit their preferences. The units operate quietly, enhancing the overall comfort of the environment without disruptive fan noise. Additionally, the CDV34NA model runs on natural gas, while the CDV34PA uses propane, providing options based on the homeowner's available gas supply.

In conclusion, the Desa CDV34NA and CDV34PA are exceptional options for those seeking a versatile and stylish heating solution. With their vent-free technology, enhanced safety features, and elegant design, these fireplaces are perfect for adding warmth and character to any indoor space. Whether for new constructions or renovations, these models offer the right blend of function and form for today's discerning homeowners.