Desa CCL3924PTA/NTA Continued, Mantel Clearances, Determining Minimum Mantel Clearance

Models: CCL3018PTA/NTA RL2718PA/NA CCL3924PA/NA CCL3924PTA/NTA CCL3930PTB/NTB CCL3018PA/NA CRL3124PA/NA

1 40
Download 40 pages 62.8 Kb
Page 10
Image 10
Accessories, page 38).

INSTALLATION

Continued

If Using Mantel

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombus- tible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). Even if noncombus- tible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and 6 and Figure 7 on page 11 for minimum clearances.

Noncombustible

Requirements for

Material

Safe Installation

Distance (A)

 

 

 

12" or more

Noncombustible material

 

okay.

Between 8"

24", 30" or 36" Models:

and 12"

Install fireplace hood

 

accessory (GA6050,

 

GA6052 or GA6053 see

 

Accessories, page 38).

 

18" Model: Noncombus-

 

tible material okay.

Less than 8"

Noncombustible material

 

must be extended to at

 

least 8". See Between 8"

 

and 12", above. If you

Mantel Clearances

In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clearances in Figure 6 you will need a hood.

Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance

When Using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Figure 7, page 11 when using hood.

NOTICE: Surface temperatures ofadjacentwallsandmantelsbe- comehotduringoperation.Walls and mantels above the firebox may become hot to the touch. If installed properly, these tem- peratures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.

cannot extend material,

you must operate heater

with flue damper open.

Heat Resistant

Material

(A)

 

 

10"

 

 

8"

 

 

 

6"

 

 

 

2 1/2"

Minimum

 

 

(A)

 

 

Noncombustible

 

Material

 

12"

 

 

 

 

 

 

8"

 

 

 

 

Mantel Shelf

18"

 

20"

22"

 

8"

 

14"

17"

 

 

 

 

Underside

of Mantel

Shelf

All minimum distances are in inches

Log Set

24"/30"

24" Mantel Clearances Models

20" Determining Minimum Mantel Clearance 18" Model

Top of Fireplace Opening

Minimum

Distances to

Noncombustible

Underside of

Material Height

Mantel

Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 11.

Figure 6 - Minimum Mantel Clearances
Without Using Hood

10

www.desatech.com

113097-01E

Page 10
Image 10
Desa CCL3924PTA/NTA, CRL3124PA/NA Continued, Mantel Clearances, Determining Minimum Mantel Clearance, When Using a Hood