INSTALLATION
Continued
CAUTION: Use only new, black iron or steel pipe. Inter-
Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 24).
IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special re- quirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves. Never use sealant on flare threads.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
External
Regulator Propane/LP
Supply Tank
Vent
Pointing
Down
Figure 24 - External Regulator with Vent
Pointing Down
We recommend that you install a sediment trap in | |||
supply line as shown in Figure 25. Locate sediment | |||
trap where it is within reach for cleaning. Install in | |||
piping system between fuel supply and fireplace. | |||
Locate sediment trap where trapped matter is not | |||
likely to freeze. A sediment trap traps moisture and | |||
contaminants. This keeps them from going into fire- | |||
place gas controls. If sediment trap is not installed or | |||
is installed wrong, fireplace may not run properly. | |||
|
| CSA | |
|
| Equipment Shutoff Valve | |
|
| With 1/8" NPT Tap* | |
|
|
| Natural |
|
|
| From Gas |
|
|
| Meter |
|
|
| (5" W.C. to |
|
|
| 10.5" W.C. |
3" Minimum |
| Pressure) | |
|
| ||
|
|
| Propane/LP |
Pipe | Cap | Tee | From External |
Nipple |
| Joint | Regulator (11" |
|
|
| W.C. to 14 " |
Sediment Trap | W.C. Pressure |
Figure 25 - Gas Connection
*Purchase the optional CSA
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
•5/16" hex socket wrench or
•Phillips screwdriver
•sealant (resistant to propane/LP gas, not provided)
1.If fireplace screen and floor are still installed, see Removing Fireplace Screen and Floor Assembly, page 9.
2.Route gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes.
NOTICE: Most building codes do notpermitconcealedgasconnec- tions.Aflexiblegaslineisprovided to allow accessibility from the fireplace (see Figure 26, page 19). The flexible gas supply line con- nection to the equipment shutoff valve should be accessible.
18 | www.desatech.com |