Desa MSRBVN Troubleshooting Venting Problems, Stove And B-Vent Burner System Installation, Elbows

Models: MSRBVP MSRBVN

1 32
Download 32 pages 40.7 Kb
Page 12
Image 12
TROUBLESHOOTING VENTING PROBLEMS

SUN VALLEY STOVE COMPANY

CAST IRON STOVE AND BURNER SYSTEM

TROUBLESHOOTING VENTING PROBLEMS

Most venting problems are caused by incor- rect vent sizing, improper installation, or inadequate air supply. A preliminary check for a field problem might include:

Using a draft meter to determine if venting system draft meets manufacturer’s specifications

Checking the vent sizing according to manufacturer’s specifications, appliance input, and venting configuration

Examining the entire venting system for faults such as disconnected joints for damaged vent sections

Making sure vent and air openings are not obstructed

If these procedures do not reveal the source of the problem, troubleshooting may include attention to common venting problems.

FLUE GAS SPILLAGE

Spillage occurs when flue gases cannot exit the vent system and back up into the dwell- ing. A primary symptom of appliances equipped with a Vent Safety Shutoff System (flue spill switch) is unexplained appliance shutoffs. Other symptoms of flue gas spillage at the draft hood include condensation on walls and windows and/or noticeable odors. Spillage may also result in the release of carbon monoxide, a colorless, odorless, highly toxic gas. A simple spillage test can be con- ducted if spillage is suspected. See Checking Gas Connection, pages 14 and 15.

CAUSES OF SPILLAGE AND CORRECTIVE ACTION

Incorrect Vent Sizing

If the vent is too small or too short, spillage may occur. If the vent is too large, excessive dilution air may cool flue gases and reduce draft, causing spillage. The vent cap size should also be checked. Check manufacturer’s instructions, appliance in- put rating, and appropriate sizing tables.

Venting Condition

Loose joints can affect draft and cause spill- age. “Mashed” vent sections and damaged vent caps can restrict flow and cause spill- age. Examine and replace as needed.

Obstructions

Small animals or birds may get into and block the vent or draft hood outlet. Dust, lint, and foreign objects may obstruct air inlets. Re- move obstructions and clean openings.

Lateral Run

Lengthy horizontal or non-vertical runs cause resistance to flow and may reduce draft enough to cause spillage. The pitch of lateral runs can also be a problem; lateral runs should be pitched 1/4" rise per foot of hori- zontal run from the appliance to the vent.

Elbows

Too many elbows cause excessive restric- tion of flow and may result in spillage. Usually, two 90º turns can be tolerated in a properly sized venting system. More than two may cause problems and necessitate changing the system.

Negative Pressure in the Dwelling

An extremely tight house may not supply adequate combustion and venting air. Use of mechanical exhaust such as a dryer vent or range vent may worsen the problem. An air exchange system must be installed in the dwelling to correct this problem.

Flue Gas Cooling

Venting exposed to extremely cold tem- peratures or venting of single wall construc- tion loses heat needed to maintain draft; massive masonry chimneys absorb needed heat. If the flue gases cool excessively, draft is reduced and spillage may result. Use proper materials, insulate and protect prop- erly, reline when necessary.

Down Drafts

In certain wind conditions and in certain relationships with nearby structures and objects, high pressure conditions may affect draft negatively. Relocate the vent cap, raise its height, or use an approved high wind cap.

STOVE AND B-VENT BURNER SYSTEM INSTALLATION

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri- mary heating system. Do not in- stall this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circu- late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

CHECK GAS TYPE

Use proper gas type for the burner system unit you are installing. If you have conflict- ing gas types, do not install burner system. See dealer where you purchased the burner system for proper system according to your gas type.

INSTALLING GAS PIPING TO FIREPLACE LOCATION

FLUE GAS SPILLAGE WARNING: A qualified in- staller or service person must connect burner system to gas supply. Follow all local codes.

CAUSES OF SPILLAGE AND CORRECTIVE ACTION CAUTION: For propane/LP units, never connect heater di- rectly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane/LP supply.

For more information, visit www.desatech.com

12

106706

Page 12
Image 12
Desa MSRBVN Troubleshooting Venting Problems, Stove And B-Vent Burner System Installation, Flue Gas Spillage, Obstructions