20
STOVE AND
Checking Gas Connections (Cont.)
STOVE AND DIRECT-VENT BURNER SYSTEM INSTALLATION
Continued
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1.Close equipment shutoff valve (see Figure 40).
2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas burner system or open- ing main gas valve located on or near gas meter for natural gas burner system, or using compressed air.
3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 41 for propane/LP or Fig- ure 42 for natural). Apply a noncorrosive leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Burner System Gas
Connections
1.Open equipment shutoff valve (see Figure 40).
2.Open propane/LP supply tank valve for propane/LP burner system or main gas valve located on or near gas meter for natu- ral gas burner system.
3.Make sure control knob of burner system is in the OFF position.
4.Check all joints from equipment shutoff valve to thermostat gas valve (see Figure 41 for propane/LP or Figure 42 for natu- ral). Apply a noncorrosive leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.
5.Light burner system (see Operating Stove with Burner System, pages 23 through 26). Check all other internal joints for leaks.
6.Turn off burner system (see To Turn Off Gas to Appliance, page 24).
Open
Equipment
Shutoff
Valve
ClosedPO
Figure 40 - Equipment Shutoff Valve
Equipment | Propane/LP |
Shutoff Valve | Supply Tank |
Gas Valve |
|
Figure 41 - Checking Gas Joints for Propane/LP Gas Burner System
Equipment
Shutoff Valve
Gas Meter
Gas Valve
Figure 42 - Checking Gas Joints for Natural Gas Burner System