VERTICALLY INTO EXISTING MASONRY FIREPLACE
NOTE: Follow Vent chimney manufacturer’s instructions.
1.Have the masonry chimney inspected by a qualified chimney sweep or installer to determine its structural condition.
2.You will need a pipe length equal to the chimney height from the hearth plus 18 inches.
3.Install a blanking plate and the chimney pipe, and if used the outside air pipe, as shown in Figure 12.
4.Attach the DuraVent adapter, a section of pipe and clean out tee, making sure the clean out tee is centered in the chimney flue area. Use RTV, metallic tape, and a minimum of three
5.Position the stove, adhering to the clearances in Figures 1 & 2.
6.Measure and build chimney top plate. Cut out holes for chimney pipe, and if used the outside air pipe. Install and seal with
3"
FOLLOW CHIMNEY OR
VENT MANUFACTURER'S
INSTRUCTIONS
VERTICAL ROOF VENT
18"
TOP PLATE
BLANKING PLATE
OPTIONAL
OUTSIDE AIR
CLEAN OUT
TEE
INSTALLATION THROUGH SIDE OF MASONRY CHIMNEY
Figure 12
Venting through masonry chimney
NOTE: Follow Vent chimney manufacturer’s instructions.
1.Position the stove, adhering to the clearances in Figures 1 & 2. Mark the center of the hole where the pipe is to pierce the masonry chimney.
2.It will be necessary to break out the masonry around the location of the pipe center mark. Use a
3.Measure and build chimney top plate. Cut out holes for chimney pipe, and if used the outside air pipe.
4.Install the tee on the bottom of the vertical pipe system and lower it down the chimney until the center branch of the tee is level with the center of the hole in the masonry, as shown in Figure 13.
5.Install and seal the top plate from step 3 with
6.Connect the horizontal pipe by pushing it through the hole in the masonry and lining it up with the branch in the tee. Push the pipe into the tee while twisting it to lock it into the tee.
7.If desired, once the horizontal pipe is in place, the space between the pipe and masonry may be filled with
Install the trim collar. An adjustable pipe length and adapter may be needed to finish the connection to the stove.
3"
FOLLOW CHIMNEY OR
VENT MANUFACTURER'S
INSTRUCTIONS
OPTIONAL
OUTSIDE AIR
WALL
THIMBLE
VERTICAL ROOF VENT
18"
TOP PLATE
CLEAN OUT
TEE
Figure 13
Venting through side of
masonry chimney
10